EN-7100 GAMEWELL-FCI [Gamewell-FCI by Honeywell], EN-7100 Datasheet - Page 2

no-image

EN-7100

Manufacturer Part Number
EN-7100
Description
Compact Analog Addressable Fire Alarm Control Panel
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Description (Continued)
Remote Station, Proprietary, and Central Station fire alarm
systems. It allows ample space for wiring and room for bat-
teries up to 7 A/H capacity.
Features (Continued)
• Alarm verification per individual sensor
• Positive alarm sequence for sensors or monitor
• Four levels of system access using six (6), digit pass-
• Duplicate and extra address indications
• March time (60 or 120 BPM)/temporal pattern/coded
• Cross zoning
• System configuration programming and 280 event log
• Fan restart with sequential restart delay
• Upload/download of panel configuration between panel
• Up to sixty-four (64), 7100 panels in the E3 Broadband
Optional Accessories
LCD-7100
The LCD-7100 remote serial display offers an 80-character
alphanumeric readout for the remote display of all system
events. It duplicates all the information on the 7100 Series
panel display and provides key switch protected functions
such as System Reset, Alarm Acknowledge, Trouble
Acknowledge, Signal Silence, and Drill Test.
LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys-
tem Trouble, Power Fault, Systems Silenced, NAC#1, and
NAC#2 Silenced conditions.
The LCD-7100 can be surface or semi-flush mounted on a
standard four-gang electrical box. It can be installed up to
4,000 feet (1,219 m) from the main control panel. The 7100
Series fire alarm control panel supports up to five (5),
remote LCD-7100 annunciators using one pair of twisted,
non-shielded 18 AWG min. wire or serial communication
and uses another pair of 16 AWG min. for operating volt-
age.
(For additional information, refer to the LCD-7100 data
sheet, Part Number: 9020-0486).
9020-0466 Rev. E2 page 2 of 3
modules
words with up to five (5), user passwords per Level
fours/California Code/user-defined zone coding
stored in non-volatile memory
and FCP-7100 program (password protected feature)
network with an optional INI-7100 Module
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
GAMEWELL-FCI
LDM-7100
The LED Driver Module (LDM-7100) is designed to mount
in a UL Listed remote annunciator and provides outputs for
remote panel switches and thirty-three (33), remote LEDs.
Three (3), LDM-7100 modules may be installed in a single
annunciator for a total of ninety-nine (99), LEDs per annun-
ciator. This combination may be repeated up to five times
for a total of fifteen (15), LDM-7100 panels installed at up to
five (5), different locations. Maximum distances of up to
4,000 feet (1,219 m) can be achieved using one pair of
twisted, non-shielded wire for serial communication and
using another pair of straight-lay wire for operating voltage.
(For additional information, refer to the LDM-7100 data
sheet, Part Number: 9020-0519).
CAOM
The Class “A” Optional Module (CAOM) allows Style Y and
Z (Class “B” and “A”) operation for both Notification Appli-
ance Circuits and allows Style 4 and 6 (Class “B” and “A”)
for both Signaling Line Circuits. It also provides disconnect
switches for each signaling line circuit and a common dis-
connect switch for both notification appliance circuits.
MCOM
The Municipal Connection Option Module (MCOM) pro-
vides three (3) choices of outputs. It can be configured as a
Municipal Circuit (City Box) output. It may also be set to
serve as a Reverse Polarity output with a nominal voltage
output of 24 VDC at 0.012 amp. maximum alarm and
supervisory current. The MCOM’s third option provides a
releasing solenoid output rated at:
• 24 VDC nominal voltage.
• 0.005 amp. supervisory current.
• 0.710 amp. maximum alarm current.
• 2 ohms maximum line resistance.
PTRM
The Printer Transient Module (PTRM) provides RS-232
Isolator/Transient protection for the 7100’s RS-232 port
(BSM connector J2). It is used in conjunction with a serial
printer applied to the RS-232 port for permanent record
keeping.
INI-7100
The Intelligent Network Interface Module allows the 7100
Series fire alarm control panel to become the platform of a
peer-to-peer, token ring, self-regenerative network com-
prised of up to sixty-four (64), 7100 panels.