H8GN OMRON [Omron Electronics LLC], H8GN Datasheet

no-image

H8GN

Manufacturer Part Number
H8GN
Description
Preset Counter/Timer H8GN C-61
Manufacturer
OMRON [Omron Electronics LLC]
Datasheet
World’s Smallest Compact Preset Counter/
Timer
1/32-mm DIN with Communications
• Only 48 x 24 x 83 mm (W x H x D)
• Switch between 4-digit preset counter and 4-digit timer opera-
• While using the preset counter, it is possible to switch the dis-
• Built-in prescaling for counter operation.
• ON/OFF-duty adjustable flicker mode that can be used to per-
• Four preset values that can be changed by the front panel key
• Finger protection terminal block to meet VDE0106/P100.
• Panel surface compatible with NEMA4X/IP66.
• Conforms to UL, CSA, and IEC safety standards as well as CE
• Six-language instruction manual provided.
Model Number Structure
I Model Number Legend
1. Supply Voltage
Ordering Information
I List of Models
H8GN-AD-@
24 VDC
tion.
play to monitor the totalizing count value (8 digits).
form cyclic control is available for timer operation.
(SV-bank).
Marking.
Preset Counter/Timer
H8GN
D:
24 VDC
Supply voltage
1
2
Contact output (SPDT)
Output
H8GN-AD
2. Communications Output Type
None: Communications not supported
FLK: RS-485
No communications
Preset Counter/Timer
Communications
H8GN-AD-FLK
H8GN
RS-485
C-61

Related parts for H8GN

H8GN Summary of contents

Page 1

... Model Number Structure I Model Number Legend H8GN-AD Supply Voltage D: 24 VDC Ordering Information I List of Models Supply voltage 24 VDC Contact output (SPDT) 2. Communications Output Type None: Communications not supported FLK: RS-485 Output No communications H8GN-AD Preset Counter/Timer Communications RS-485 H8GN-AD-FLK H8GN C-61 ...

Page 2

... SPDT contact output 250 VAC/30 VDC, resistive load (cos φ VDC (failure level reference value) External, manual, and power supply resets (for timer modes) 260 ms max. (Inputs cannot be received during sensor wait time if control outputs are turned OFF.) H8GN ...

Page 3

... UL508, CSA C22.2 No.14 Conforms to EN61010-1/IEC61010-1 (Pollution degree 2/overvoltage category II) Conforms to VDE0106/P 100 (Finger Protection) Rear section: Gray smoke; Front section: N1.5 (black) Panel surface: IP66 and NEMA Type 4X (indoors) Rear case: IP20 Terminal block: IP20 Approx Preset Counter/Timer H8GN C-63 ...

Page 4

... Error detection (See note.) Flow control Interface Retry function Communications buffer Reading and writing from H8GN Note: The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the communications setting level. I Life-test Curve (Reference Values) Resistive Load 1,000 ...

Page 5

... During resetting, timing stops and the control output turns OFF. • The RST indicator is lit during resetting. • Prohibits timing operation. • Output made according to the output mode setting when the set value is reached. Preset Counter/Timer H8GN C-65 ...

Page 6

... No. 2 Display Displays set value or set value of the parameter. Displays the rightmost 4 digits of the count value (8 digits) when the H8GN is used as a totalizing counter. (Zeros suppressed) Up/Reset Key Each press of this key increases values displayed on the No. 2 display. Hold down this key continuously to increase values quickly ...

Page 7

... Insert the H8GN in the square cutout, insert the adapter from the back, and push the H8GN into the cutout as far as possible. Use screws to secure the H8GN. To make the H8GN waterproof, insert waterproof packing and tighten the screws. ...

Page 8

... In applications where a set value of 258 ms or less is required, use start timing with signal input. When the H8GN is used with power start in F mode (i.e., accumula- tive operation with output on hold), there will be a timer error (approx- imately 100 ms each time the H8GN is turned ON) due to the characteristics of the internal circuitry ...

Page 9

... IP66). In order to prevent the internal circuit from water penetration through the space between the Counter and oper- ating panel, attach a rubber packing (provided with the H8GN) between the Counter and operating panel and secure the rubber packing with the Y92F-34 Flush-mounting Adaptor. ...

Page 10

... Keys are used to switch between setup menus, and the amount of time that you hold the keys down for determines which setup menu you move to. This section describes two typical examples. Note: In the following sections, “PV” is used to indicate a present value and “SV” to indicate a set value. 1. Using the H8GN as a Counter Typical Application Examples 1. Changing Set Values ...

Page 11

... Using the H8GN as a Timer Typical Application Examples 1. Changing Set Values Set value and selections in each display can be changed by pressing the and Keys. 2. Display No. 1 Display No. 2 Display Typical Application Examples Time range 0.0 to 999.9 s Timer mode DOWN (remaining time) Output mode ...

Page 12

... This level is for initializing settings, enabling SV-bank and totalizing counter use, setting display auto-return time, and move- to-protect- level time. • You can move to the initial setting level from this level. H8GN Operation in progress Operation stopped Not displayed depending on model and settings. ...

Page 13

... Communications writing control ( ( ( ( (3) Cycle time Cycle time Close Open Fully closed to Valve fully open ON duty 0% to 100% Set ON duty rate as a percentage ON duty can be changed like an analog input by using the Up and Down Keys. H8GN Preset Counter/Timer C-73 ...

Page 14

... Time Range (timr) The time range is displayed only when “Counter/Timer selec- tion” in the initial setting level has been set to timer. When the H8GN used as a timer, set the time range to be timed. 4. Timer Mode (timm) The timer mode is displayed only when “Counter/Timer selection” ...

Page 15

... The input signal edge will be displayed only when the “input mode” at the initial setting level has been set to increment or decrement. Switches the CP1 input edge when the H8GN is used as an incre- menting or decrementing counter. In the counter increment or decrement modes, CP2 will function as the gate input and CP1 counting will be prohibited while CP2 is ON ...

Page 16

... Reset Key Protect (rpt) Prohibits the use of the Reset Key. Setting OFF ON The default setting is OFF. H8GN (1) Operation/Adjustment Protection Restricts menu display and writing in the operation and adjustment levels. (2) Initial Setting/Communications Protection Restricts menu display and moving to the initial setting level/communications setting level/advanced function setting level ...

Page 17

... Communications Data Length (len) The communications data length can be changed to either bits. 4. Stop Bits (sbit) The stop bits can be set to either Parity (prty) Set value The parity can be set to none, even, or odd 9 euen / H8GN Preset Counter/Timer C-77 ...

Page 18

... When counter selected When counter selected When increment or decrement selected in counter input mode See note 3. H8GN Power ON Key less than 1s. Operation level See note 1. PV/SV Press the Key to PV reset the PV. Press the Key to reset the totalizing count value and Totalizing count value ...

Page 19

... Timer (cycle time or mode other than output mode Z) : 0.000 to 9.999 s : 0.00 to 99. 0.0 to 999.9s, min 9999 min min min min Timer (output mode 100% (ON duty) : -.---s : --.--s (default) : ---.-s : ----s : --min--s : ---.-min : --h--min : ---.-h : ----h H8GN C-79 ...

Page 20

... Short-circuited L Open C-80 Preset Counter/Timer up CP1: Count input Count prohibit Count CP1: Count input Count prohibit ud-b) ud-b ud-b Count Input H8GN Down (Decrement) mode (down down) down down CP2: Count prohibit input Count prohibit n n-1 n-2 n-3 CP2: Count prohibit input Count prohibit n n-1 n-2 Count Up/Down C quadrature input (ud-c ...

Page 21

... PV. • When totalizing count value is reset, the PV is reset at the same time. • The totalizing count range 99,999,999. If the totalizing count exceeds 99,999,999, the count returns the count drops below 0, it becomes 99,999,999. H8GN Preset Counter/Timer t C-81 ...

Page 22

... Power supply Start Gate Reset Control output DOWN 0 Z mode: ON/OFF-duty adjustable flicker Power supply Start Gate Reset Control output Cycle time ON duty setting (%) ON time UP 0 Cycle time ON duty setting (%) ON time DOWN 0 H8GN B mode: Flicker (See note.) E mode: Interval ...

Page 23

... Note: Error codes are displayed only if PV/ being displayed. Error contents Memory error (RAM) Turn the power OFF and ON again. If normal operation is still not restored, it may be necessary to repair or replace the H8GN. If normal operation is Memory error (EEP) restored by turning the power supply OFF and ON possible that there CPU error is noise interference ...

Page 24

... Same as for PV in the above PV/SV column 99999999 0/1/2/3 H8GN Default Unit Set value value 0 1 off off Default ...

Page 25

... Setting range Default value 1 9 eUen Preset Counter/Timer Unit Set value Second Second Second Second Minute: Sec- ond Minute Hour: Minute Hour Hour Unit Set value Second Second Second Unit Set value kbps bit bit H8GN C-85 ...

Page 26

... To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. Cat. No. M065-E1-02 C-86 Preset Counter/Timer Setting range on/off on/off on/off off H8GN Default Unit Set value value off off off off Second Second ...

Related keywords