ADM-24 GAMEWELL-FCI [Gamewell-FCI by Honeywell], ADM-24 Datasheet

no-image

ADM-24

Manufacturer Part Number
ADM-24
Description
Fire Alarm Control Panel with built-in DACT and remote-site upload/download capability
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Flex 405
Fire Alarm Control Panel with built-in DACT
and remote-site upload/download capability
Flex 405 CS-2405 09/01/06
contacts to trigger five channels). Selectable transmission formats allow the
Flex 405 to communicate to virtually all central stations.
Remote-Site Upload/Download
The Flex 405 may be downloaded or uploaded without affecting the system fire
protection. Download system programming, and upload key system information
such as: current system status, history and walk test files; zone, AC line, NAC
1 and NAC 2, resettable power and battery voltages; and system programming.
Upload or download within one minute without affecting normal fire panel func-
tions. The upload/download function also features multiple security techniques.
The Flex 405 requires the PK-CD programming kit, which works with most Hayes-
compatible modems (consult factory for listing).
405 may be used in a variety of cost-
effective applications, including: local
fire alarm control panel (communica-
tor disabled), fire alarm control panel/
communicator, stand-alone sprinkler
supervisory communicator, or slave
communicator to a UL-Listed host fire
alarm panel (requires normally-open dry
Description
The Gamewell Flex 405 is a 24-volt,
five-zone Fire Alarm Control Panel
FACP) with built-in communicator and
remote-site upload/download capabil-
ity. The integral communicator trans-
mits event information (alarms,
troubles, supervisories, faults, etc.) to
a UL-Listed central station. The Flex
Page 1 of 4
Features
• Five programmable Initiating Device Circuits
• Two built-in, Class A or B (Style Z or Y)
• 3.0 amps of notification appliance power,
• Two built-in Form-C Alarm and Trouble relays.
• Supervisory and communication fail outputs.
• Dual-line rotary- or Touch-Tone®-dial DACT
• 24-Volt operation.
• Built-in voltmeter measures: zone voltage;
• Surface Mount Technology (SMT).
• Fully programmable via built-in keypad (no
• Complies with NFPA 72 (Local, Central
• Reporting formats include:
• Integral battery charger for up to 60 hours of
• Fuseless, power-limited technology meets
• Programmable alarm presignal timer, alarm
• Single-person walk test. Fire drill function.
• Zone disable capability (software).
• 32-Event history buffer with time-and-date
• Extensive built-in transient protection.
• Electronics and operational controls fully
• Optional: contact-by-zone module, remote
Listings
• UL Listed.
• CSFM approved: file 7165-1288:179.
• MEA approved: file 366-04-E.
(zones). Each zone may be programmed for:
two-wire smoke detectors, normally open
contact devices (pull stations, heat detectors),
four-wire smoke detectors, waterflow
operation, supervisory operation, auto-reset
supervisory operation.
Notification Appliance Circuits (NACs).
NACs may be programmed: silenceable,
non-silenceable (a strobe circuit can keep
flashing after the panel is silenced), auto-
silence (program 5 to 30 minutes), silence
inhibit (60 seconds), coding (march time,
temporal, California).
expandable to 5.0 amps (meets the critical
power requirements for ADA and UL-1971
devices).
interfaces to public telephone network (leased
phone lines are not required).
primary AC line voltage; battery voltage;
NAC(s) voltage; resettable 24-volt power.
costly external programmers necessary).
Station and Remote Station [DACT only – not
polarity reversal] Fire Alarm Systems).
3+1, 4+1, 4+2 Standard + Expanded;
4+1, 4+2, Ademco Express.
standby power.
UL power-limiting requirements.
verification timer, and optional trouble
reminder.
stamp. Accurate real-time clock/calendar.
enclosed in a lockable cabinet capable of
housing up to 7 AH batteries.
annunciator, printer interface for on- or off-line
printing.
Listings and approvals below apply to the
basic Flex 405 panel. In some cases, certain
modules may not be listed by certain
approval agencies, or listing may be in
process. Consult factory for latest listing
status.

Related parts for ADM-24

ADM-24 Summary of contents

Page 1

Flex 405 Fire Alarm Control Panel with built-in DACT and remote-site upload/download capability contacts to trigger five channels). Selectable transmission formats allow the Flex 405 to communicate to virtually all central stations. Remote-Site Upload/Download The Flex 405 may be downloaded ...

Page 2

... XRM-24 120 VAC, 100 VA transformer expands NAC power from 3.0 to 5.0 amps. SAN-405 Five-zone remote annunciator (RZA-5F), mounts to a single- gang box (requires ADM-24). ADM-24 Annunciator driver module (supports SAN-405). RM-5F Five-zone relay module, provides contact-by-zone. CAC-5F Class A converter module. Converts all Class B initiating device circuits (zones) to Class A ...

Page 3

UL-Listed Receivers Compatible with the Flex 405 Format # (Addresses 16 & 42) 0 4+1 Ademco Express 1 4+2 Ademco Express 2 3+1/Standard/1800/2300 3 3+1/Expanded/1800/2300 4 3+1/Standard/1900/1400 5 3+1/Expanded/1900/1400 6 4+1/Standard/1800/2300 7 4+1/Expanded/1800/2300 8 4+1/Standard/1900/1400 9 4+1/Expanded/1900/1400 A 4+2/Standard/1800/2300 B ...

Page 4

Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2006 Gamewell-FCI Notes Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their ...