Specifications
■ Ratings
Item
Operating voltage range
Power
consumption
Sensor input
Input impedance
Control
output
Alarm output
Event input
Control method
Setting method
Indication method
Other functions
Ambient operating
temperature
Ambient operating humidity
Storage temperature
E5CN
E5CN-U
Relay output
Voltage output E5CN
Current output E5CN
Long-life relay
output
Contact input
Non-contact
input
Power supply
voltage
85% to 110% of rated supply voltage
7.5 VA max. (E5CN-R2T: 3.0 VA at 100 VAC)
6 VA max.
Models with temperature inputs
Models with analog inputs
Current input: 150 W , Voltage input: 1 M W (Use a 1:1 connection when connecting the ES2-HB.)
E5CN
E5CN-U
E5CN-U
E5CN
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 1 V, 1 mA
ON: 1 k W max., OFF: 100 k W min.
ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Outflow current: Approx. 7 mA per point
ON/OFF control or 2-PID control (with auto-tuning)
Digital setting using front panel keys
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: PV: 11 mm, SV: 6.5 mm
Manual output, heating/cooling control, transfer output (on some models), loop break alarm, multi SP, MV
limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, etc.
- 10 to 55 ° C (with no icing or condensation), for 3-year warranty: - 10 to 50 ° C
25% to 85%
- 25 to 65 ° C (with no icing or condensation)
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Thermocouple: K, J, T, E, L, U, N, R, S, or B
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70 ° C, 60 to 120 ° C, 115 to 165 ° C, or 160 to 260 ° C
Voltage input: 0 to 50 mV
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Output voltage: 12 VDC ± 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 600 W max., resolution: approx. 2,700
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, minimum applicable
load: 5 V, 100 mA (Do not connect a DC load.)
100 to 240 VAC, 50/60 Hz
Digital Temperature Controllers
5 VA/3 W max. (E5CN-R2T: 2.7 VA at 24 VAC)
3 VA/2 W max.
24 VAC, 50/60 Hz or 24 VDC
E5CN/E5CN-U