E5C2 OMRON [Omron Electronics LLC], E5C2 Datasheet - Page 2

no-image

E5C2

Manufacturer Part Number
E5C2
Description
DIN-sized (48 x 48 mm) Temperature Controller with Analog Setting
Manufacturer
OMRON [Omron Electronics LLC]
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
E5C2-R
Manufacturer:
WAW
Quantity:
2 000
Part Number:
E5C2-R20K
Manufacturer:
Kingston
Quantity:
1 000
Specifications
I Ratings
Note: Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.
I Input Ranges
Note: 1. Values in ( ) are the minimum unit.
I Characteristics
Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
I-6
Supply voltage
Operating voltage range
Power consumption
Input
Control mode
Setting method
Indication method
Control output
Range
Setting accuracy
Hysteresis
Proportional band
Control period
Reset range (see note 1)
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
Degree of protection
Weight
2. Values in ( ) are the thermistor resistive value.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.
Input
Temperature Controller
C
F
0 to 200 (5),
0 to 300 (10),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20),
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)
Chromel vs. alumel
K (CA)
Approx. 0.5% FS (fixed)
3% FS (fixed)
Approx. 20 s
5 1% FS min.
20 M
2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
Malfunction: 147 m/s
Destruction: 294 m/s
Electrical:
Operating: –10 C to 55 C (with no icing or condensation)
Operating: 45% to 85%
Front panel: IEC standard IP40 (see note 2)
Terminals:
Approx. 200 g (with flush-mounting adapter)
2% FS max.
100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
50/60 Hz (common)
90% to 110% of rated supply voltage
Approx. 2 VA
Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor
ON/OFF or P control
Analog setting
No indication
Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
E5C2
Thermocouple
min. (at 500 VDC)
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20)
100,000 operations min. (3 A at 110 VAC, resistive load)
IEC standard IP00
Iron vs. constantan
2
2
, 3 times each in 6 directions
, 3 times each in 6 directions
J (IC)
–50 to 50 (2),
–20 to 80 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
32 to 212 (5),
32 to 392 (10)
Platinum resistance
thermometer
Pt100
–50 to 50 (2) (6 k
0 to 100 (2) (6 k
50 to 150 (2) (30 k
100 to 200 (2) (550
150 to 300 (2) (4 k
---
Thermistor (see note 2)
THE
at 0 C),
at 0 C),
at 0 C),
at 200 C)
at 200 C),

Related parts for E5C2