tector clockwise until the detector locks into place.
on the scribed line in the tamper proof tab located on the
detector mounting bracket. Install the detector. To re-
move the detector from the base when using the tam-
per-proof feature, insert the blade of a small
screwdriver into the hole on the side of the base and
push the plastic lever away from the detector head. This
will allow the detector to be rotated counterclockwise
for removal. NOTE: The decorative ring must be re-
moved in order to remove the head when using the tam-
per-proof feature.
nently by breaking the plastic lever off the base.
which can be accommodated per zone varies with dif-
ferent control panels. Consult the control panel in-
struction manual to determine the capacity.
Detectors” for spacing, location of detectors and other
guidelines.
Place the detector into the detector base. Turn the de-
To use the tamper-proof feature, break the smaller tab
The tamper-proof feature may be defeated perma-
NOTE: The number of two-wire smoke detectors
Refer to NFPA 72, Chapter 5-3, “Smoke Sensing Fire
Detectors may be tested in the following ways:
2 of 2
On a 4-inch square box with or without plaster
ring. Minimum depth 1.5 inches.
On a 3.5-inch octagonal box. Minimum depth
1.5 inches.
Place a test magnet against the detector
as directed in the installation instructions.
The detector should go into alarm within
30 seconds.
Field metering of detector sensitivity may be
performed with the aid of a voltmeter and Test
Kit, MOD 400R. For the complete procedure,
refer to the Installation and Maintenance
Instructions furnished with each detector.
INSTALLATION
Model
1151
B110LP
B112LP
B114LP
B401BH
RA-400Z
PAM-1
MOD 400R
MOUNTING
TESTING
ORDERING AND TECHNICAL INFORMATION
Contacts
Form A & C
Form A, C & Supv.
Form B
Description
Ionization Detector
Base, Two-wire
Base, four-wire, 24 VDC operation
Base, four-wire, 120 VAC operation
Base, four-wire, with audible sounder
Remote Alarm Indicator
End of Line Relay, 24 VDC
Test Kit
ual environment. We recommend at least an annual
cleaning of the unit. The detector screen and cover as-
sembly can be removed, revealing the sensing cham-
ber. A vacuum cleaner can be used to remove dust from
the screen, cover and sensing chamber. For the com-
plete procedure, refer to the Installation and Mainte-
nance Instructions furnished with each detector.
Cleaning programs should be adapted to the individ-
MAINTENANCE
9020-0582