EDS11-101E FUJI [Fuji Electric], EDS11-101E Datasheet - Page 3

no-image

EDS11-101E

Manufacturer Part Number
EDS11-101E
Description
FC SERIES COMPACT CONTROLLER S(STEP OUTPUT TYPE)
Manufacturer
FUJI [Fuji Electric]
Datasheet
5. Power failure processing functions
Power failure detection:
During power failure:
Power failure recovery time:
6. Self-diagnosis function
Computation/control circuit abnormality:
Input/output signal abnormality, manipulated output
disconnection:
Fault contents indication:
7. Transmission functions
(1) Transmission items
Supervisory items:
Setting operation items:
(2) Transmission setting inhibit:
(3) Transmission interface:
1) CC data line:
Interface:
Control stoppage at power failure detec-
tion
Operating parameters backed up by ca-
pacitor when power faulure occurs wthin
5 minutes
Initial set point and manipulated output
values, PID parameters, etc. are stored in
nonvolatile memory (lasts for 10 years or
longer at ambient temperature of 50 C or
less).
Initial or continuous start set for power
failure within 5 minutes.
Recovery from power failure lasting longer
than 5 minutes is done by initial.
* Operation mode at initial set.
FLT indicator lights, FLT contact output
turns "ON", and computation and control
stop.
Manipulated output can be controlled
manually at FLT (soft manual).
FLT indicator lights, control stops and
manipulated output is held. Computation
processing and output processing other
than for manipulated output continue.
Cause of fault is indicated numerically on
numerical indicator on front of the panel.
From PNC to host
Process variable, set point, manipulated
output, deviation, operation mode, alarm
information, PID parameters, various
limiter values, constants, segmented line,
analog input/output, digital input/output,
etc.
From host to PNC
Set point, manipulated output, operation
mode, PID parameters, various limiter
values, constants, segmented line, etc.
Parameter setting enable/inhibit can be
designated by transmission from the host.
Designation is made by using F/S,
CC data line or RS422 interface select
Connected with transmission controller
(PMN)
PMN and PNA; CC data line (PMN and
host RS-232C)
M: Manual mode
A: Auto mode
R: Remote mode
SCC: SCC mode
, ST keys on the front of the panel.
,
,
2) RS-422:
8. Other functions
Data protection function by use of pass code
9. Operating conditions
Power supply:
Power consumption:
Dielectric strength:
Insulation resistance:
Ambient temperature:
Ambient humidity:
Enclosure:
Enclosure class: Front IP65 (IEC 529)
Name plate:
Dimensions:
Mass {weight}:
Mounting method:
Finish color:
Range of delivery:Controller and mounting bracket
Items prepared separately:
Transmission speed:
No. of units to be connected:
Transmission distance:
Transmission form:
Code format:
Transmission speed:
No. of units connectable:
Code format: Stop bit .... 1 or 2 bit
19.2 KBPS
15 max.
500m max.
Multi-drop
12 bit binary
Universal interface
2400, 4800, 9600, 19200BPS, select-
able
31 max.
Parity bit ... Even, odd or none
Select from the following 3 types
24V DC (20 to 30V)
100V AC (85 to 132V/47 to 63Hz AC)
200V AC (187 to 264V/47 to 63Hz AC)
Approx. 12W (DC)
Approx. 20VA (AC)
1500V AC, 1 min.
500V DC, 100M
0 to 50 C
90% RH or less
Steel case
100 (H) x 70 (W), white acryl
144 (H) x 72 (W) x 391 (D) mm, IEC
(DIN) standards
Approx. 2.9kg
Flush on indoor panel, vertical mounting
is standard practice.
Mounting on tilted surface possible (angle
Munsell N1.5 for the both of front and
case.
Transmission cable (Type PNZ)
)
=0 to 90
or more
3

Related parts for EDS11-101E