EDS11-108B FUJI [Fuji Electric], EDS11-108B Datasheet - Page 3

no-image

EDS11-108B

Manufacturer Part Number
EDS11-108B
Description
FC SERIES COMPACT CALCULATOR
Manufacturer
FUJI [Fuji Electric]
Datasheet
2. Input signal
(1) Analog input signal Al
Voltage input
signal
Current input
signal
Thermocou-
ple input
Resistance
bulb input
Note: *FS: Full scale
(2) Analog input signal: 4 points
Analog input
Analog input
Analog input
Analog input
(3) Digital input signal: 4 points
Digital input
Digital input
Digital input
Digital input
(4) Pulse width or pulse number input signal: One set
Pulse width
input signal
Pulse num-
ber input
signal
3. Output signal
(1) Current output signal: One point
Current output
(2) Analog output signal: 4 points
Analog output
Analog output
Analog output
Analog output
(3) Digital output signal: 6 points
Fault output
Digital output
Digital output
Digital output
Digital output
Digital output
4. Internal uniform data conversion
(1) Analog data
0.00 to 100.00%
Standard
One input selectable from the following
PI
PI
I
I
I
AO1
AO2
AO3
AO4
DO1
DO2
DO3
DO4
DO5
AI2
AI3
AI4
AI5
+
FLT
0
DI1
DI2
DI3
DI4
+
MI
MI
1 to 5V DC
4 to 20mA DC
Type
J :0 to 600 C
K:0 to 1200 C
E:0 to 800 C
R:0 to 1600 C
Jpt100,
Pt100
–50 to 500 C
+
Contact input
(photo-coupler
insulation)
Contact input
(photo-coupler
insulation)
1 to 5V DC
Open collector output
(Photo-coupler insulation)
1 to 5V DC
4 to 20mA DC
Minimum
–327.6%
1
:
Input resistance: 1M or more;
accuracy: 0.2%/FS(*)
24V 2V DC can be supplied to
transmitter when using AC
source (approx. 35mA); accuracy:
10mV DC span or more; cold
junction compensation
comprised
accuracy:
50 C span or more; accuracy:
ON/0V, OFF/24V (input current
approx. 11mA/24V DC)
ON/0V, OFF/24V (approx.
11mA/24V DC); input max.
frequency: 500Hz
Output resistance: 1 or less;
accuracy: 0.2%/FS
0. 2%/FS
0.5%/FS
Input resistance: 1M or more
Accuracy: 0.2%/FS
ON/0V, OFF/24V (input current
approx. 11mA/24V DC)
Allowable load resistance:
600 or less; accuracy:
0.2%/FS
0.5%/FS
Output rating
30V x 0.1A DC
max.
Maximum
327.67%
(2) Digital data
Input/output status
ON (contact closed)
OFF (contact open)
5. Indication, setting, operating functions
(1) Bargraph indication
Indication type
No. of segments
Range
Resolution
Scale length
Indication mode
(2) Run mode indication
Indicating method:
(3) Numerical indication, setting
Indication method:
Indication contents:
Setting method: By operation of F/S ,
6. Power failure processing function
Power failure detection:
During power failure:
At power recovery:
7. Self-diagnosis functions
Computing circuit fault:
Input/output signal fault, run output disconnection:
Fault contents indication:
LED (red); red, H/L
LED (red), name 3 digits+numerals 5
digits (including negative sign)
Indication contents such as constants,
segmented line and wafers selectable by
keys on the front.
Calculation stops at power failure detec-
tion.
Operating parameters retained by capa-
citor backup within 5 minutes. Constants,
segmented line, wafers, parameters etc.
are stored in non-volatile memory (lasts 10
years expected at ambient temperature
below 50 C).
Initial or continuous start mode can be set
within 5 minutes. Recovery from power
failure lasting longer than 5 minutes is
done by initial.
H, L lamp simultaneously lit FLT contact
output ON, computation stops
H, L lamp simultaneously lit; FLT contact
output ON, computation and output proc-
essing for other than run output continue.
Cause of fault is numerically indicated on
front-panel numerical indicator
F/S ,
RV indicator
LED (red)
101+2
0 to 100% linear
1%/FS
100mm
0 to 100% bargraph indication
0 to 100% reverse bargraph indication
dot indication
–50 to +50% deviation indication
0.01%
0.00%
Data
and
keys on the front.
GV indicator
101+2
0 to 100% linear
1%/FS
100mm
LED (green)
,
,
, and ST
3

Related parts for EDS11-108B