3.2 Digital output (DO)
(1) Number of outputs:
(2) Output specifications:
(3) Output functions:
(4) Output cycle: 200ms
3.3 Auxiliary analog output (re-transmission output)
(1) Number of points: Up to 1 point
(2) Type:
(3) Output cycle: 200 ms
(4) Output contents:
(5) Additional function:
(6) Limitation:
[5] Motorized valve control output
Relay contact output
Up to 3 points (shared common)
Up to 2 points (independent common)
Relay contact output
Mechanical life: 20 million operations MIN.
(100 operations/min)
Electrical life: 100,000 operations MIN.
(rated load)
Alarm output (see "Alarm function")
Main unit control mode output, program
status output, etc.
Current/voltage output (0 to 20 mA DC/4
to 20 mA DC/0 to 5 V DC/1 to 5 V DC/
0 to 10 V DC/2 to 10 V DC)
• Guaranteed output range: 0 to 20.6 mA
• Accuracy:
• Linearity:
• Resolution: 5000 MIN.
• Load resistance: 600
PV, SV, DV, MV
Scaling function
Not selectable when using control output 2
DC/0 to 10.3 V DC
or smaller)
or smaller)
• Contact structure: 2 NO (SPST) con-
• Contact capacity: 220 V AC/30 V DC,
• Minimum ON/OFF current: 100 mA
• Mechanical life: 20 million operations
• Electrical life: 100,000 operations
• Output interlock: Unavailable
Contact structure: 1 NO (SPST) con-
tact
Contact capacity: 220 V AC/30 V DC, 1
A
Minimum Open/Close current: 100 mA
(24 V DC)
tacts
1 A
(24 V DC)
MIN. (100 operations/min)
MIN. (rated load)
0.2%FS ( 5%FS at 1 mA
0.2%FS ( 5%FS at 1 mA
10 k
MAX. (current)
MIN. (voltage)
4.1 Display unit
(1) Type:
(2) Indication contents:
4.2 Setting section
(1) Type:
(2) Number of keys: 4 keys.
5.1 Control types
(1) 2-position control (set parameter P to 0%)
(2) PID control (fuzzy PID included)
(3) PID dual (heating, cooling) function (fuzzy PID included)
(4) Motorized valve control (servo) without position feed-
5.2 Control parameters
• Proportional band (P):
• Integral time (I): 0 to 3200 sec. Integral time control in-
• Differential time (D):
• Control cycle:
• Anti-reset windup:
• Hysteresis band:
• Number of SV and PID combinations:
5.3 Control mode
(1) Mode type:
(2) Mode changeover:
4. Indication/setting section
5. Control functions
back
Auto
A u t o / M a n u a l
A u t o / M a n u a l
LED
Process value indication: 7 segments, 4
digits [red]
Setpoint indication: 7 segments, 4 digits
[green]
Indication status: 6 indicator lamps
Sheet type keys (with emboss)
• PID parameters determination: Auto tuning,
• PID parameters determination: Auto tuning
• Full stroke time: 30 sec MIN.
0.0 to 999.9%. 2-position control when
P = 0.
validated when I = 0.
0.0 to 999.9 sec. Differential time con-
trol invalidated when D = 0.
200 ms
0 to 100% of measurement range
50% of measurement range (at 2-posi-
tion control only)
8 combinations.
Changed by any of parameter setting,
digital input, communication and user
function keying
Auto, Manual, Remote
bumpless
bumpless
key
SEL ,
Selftuning
Manual: Balanceless · bumpless
,
R e m o t e : B a l a n c e ·
R e m o t e : B a l a n c e ·
plus user function
3