EDS11-165A FUJI [Fuji Electric], EDS11-165A Datasheet
EDS11-165A
Related parts for EDS11-165A
EDS11-165A Summary of contents
Page 1
... Lateral connecting with connectors Max. 64 [when 24V DC is applied] Power supply ↔ all terminals 1000V AC 1 min. Relay contact ↔ all terminals 1500V AC 1 min. Others 500V AC 1 min. UL, C-UL, CE marking, RoHS directive [Pending for UL, C-UL marking] EDS11-165a Date Apr. 1, 2011 ...
Page 2
PUMA/B 2. Input 2.1 Process value input (1) No. of input points (1 point/channel) (2) Input setting: Input code selection (3) Input signal: See table 1 Select from group depending on the model code. ...
Page 3
Communication function 4.1 RS-485 interface (1) Communication standards: RS-485 compatible (2) No. of port: 1 port (3) Communication, synchro method: Two-wire, half-duplex, asynchronous cycle (4) Communication speed: 9.6k, 19.2k, 38.4k, 115.2kbps (5) Communication distance: 1km (38.4kbps or less), 250m ...
Page 4
PUMA/B 10. Structure (1) Installation method: DIN rail mounting or mounting with M3 screws inside a cabinet (2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm (excluding terminal cover and projected part) (3) Weight: Approx. 200 g (4) ...
Page 5
CODE SYMBOLS [Control module (4 channels)] Digit Description 4 < Module type > 4ch control module < Input type > 5 Thermocouple / resistance bulb [all channels] Voltage / current [all channels] Thermocouple / resistance bulb [ch 1, 2], voltage ...
Page 6
PUMA/B [Table 1] Input type and standard nput range Input Input type code Resistance bulb Pt100Ω 2 (IEC Thermocouple ...
Page 7
OUTLINE DIAGRAM (Unit : mm) Front terminal cover (Option) (10) CT-input connectors Terminal block 30 (at attach/detach) LOADER STATION 1.5 6 Terminal screw M3 At mounting to the DIN rail Dimensions for screw mounting (30) 9±0.2 2-M3 +0.7 30 +0.2 ...
Page 8
PUMA/B Heater current detector (CT) Specification : CTL-6-S-H Type : 21 15 φ5 Specification : Type : 2.8 φ3.5 M3, depth 4 CTL-12-S36-8 φ2.36 30 φ ...
Page 9
TERMINAL CONNECTION DIAGRAM Loader interface plug (RS-232C GND φ2.5 3-pole miniature plug * Input 3 and Input 4 are not available for model PUMB Voltage RTD ...
Page 10
PUMA/B Operation parameter Parameter (name) SV value MV value Manual mode switch Run/Standby switch Remote mode switch Auto-tuning RUN command Digital output latch release command ALM1 set value 1 ALM1 set value 2 ALM2 set value 1 ALM2 set value ...
Page 11
Setup parameter Parameter (name) PV input type 0: Not selectable 1: Not selectable 2: Pt100 (0 to 150°C) 3: Pt100 (-150 to 300°C) 4: Pt100 (-150 to 850° 400° 800° ...
Page 12
PUMA/B System parameter Parameter (name) Current output range Output type Outout proportion cycle Output master Station No. Output master Ch. No. Output scaling span Output scaling base Output shutdown DI-1 function select DI-2 function select DI-3 function select DI-4 function ...
Page 13
System parameter Parameter (name) DO3 option function setting (bit data : 0000 to 1111) bit 0: Alarm latch function bit 1: Error input alarm function bit 2: Non-excitation output function bit 3: Hold reset function DO4 output ...
Page 14
PUMA/B Communication parameter Parameter (name) RS-485 Parity setting RS-485 Communication speed RS-485 Communication permission RS-485 Response interval time Enhanced communication module (PUMC) connection Master/slave setting in connected modules User address 01 User address 02 User address 03 User address 04 ...
Page 15
Confi guration parameter Parameter (name) Control when input burnout is detected 0: Stop control 1: Continue control LED2 Lamp Allocation 0 to 255 LED3 Lamp Allocation 0 to 255 LED4 Lamp Allocation 0 to 255 LED5 Lamp Allocation 0 to ...
Page 16
PUMA/B [Appendix A] Output limiter type setting Read/write date setting range 0: 103% / -3% , 103% / -3% 1: Limit / -3% , 103% / -3% 2: 103% / Limit , 103% / -3% 3: Limit / Limit , ...