APS1250 Tripp Lite, APS1250 Datasheet - Page 2

INVERTER W/BATT CHARGE 1250W

APS1250

Manufacturer Part Number
APS1250
Description
INVERTER W/BATT CHARGE 1250W
Manufacturer
Tripp Lite
Series
PowerVerter® APSr
Type
Inverter, UPSr
Datasheet

Specifications of APS1250

Rohs Status
Not applicable
Voltage - Output
120VAC
Voltage - Input
12VDC, 120VAC
Ac Outlets
2
Connector - Ac Output
NEMA 5-15R
Connector - Voltage Input
Terminals, Power Cord (NEMA 5-15P)
Power - Output Continuous
1250W
Power - Output Surge
2500W
Remote Capability
Yes
Region Utilized
North America
Size
9.00" L x 8.75" W x 7.00" H (228.6mm x 222.3mm x 177.8mm)
Features
Auto Power Transfer for UPS Mode, Battery Charger
Weight
23 lbs (10.4kg)
Ac Output Connector
NEMA 5-15R
Voltage - Input Connector
Terminals, NEMA 5-15P
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
TL104
Specifications
OVERVIEW
Intended
Application
OUTPUT
Frequency
compatibility
Output watts
Continuous output
capacity (watts)
Peak output
capacity (watts)
Output nominal
voltage
Output voltage
regulation
Output frequency
regulation
Overload
protection
Outlet quantity /
type
INPUT
Recommended
Electrical Service
16.6 millisecond automatic transfer between line and battery power supports UPS protection during blackouts and voltage fluctuations for
equipment compatible with a one cycle transfer time
1250 watts continuous AC output in inverter mode, 1440 watts continuous AC output in AC mode
Double Boost™ inverter output supports momentary startup loads up to 200% of the continuous rating for up to 10 seconds
OverPower™ inverter output supports longer duration overloads to 150% for 1-60 minutes under ideal battery and temperature conditions
(For best results, utilize OverPower usage for as short of a duration as possible, ensure battery bank and cabling is able to provide full
nominal DC voltage under load and allow inverter/charger to fully cool before and after OverPower usage).
3 stage, 30 amp battery charger with adjustable settings for wet/gel battery types offers fast, reliable battery recharging
Protected hardwire bolt-down input lugs safely accept heavy gauge input wiring from attached battery bank
Two built-in NEMA 5-15R output receptacles pass 120V line power or inverter output through to connected equipment
Reliability enhanced large-transformer design with secure mounting flanges and protected DC wiring terminals
Moisture-resistant construction enables vehicular or marine operation in high humidity environments
3 position operating mode switch supports "AUTO" mode to enable automatic transfer between DC and AC modes, CHARGE-ONLY to
maintain a full battery charge when AC is present without auto transfer and SYSTEM OFF settings.
Set of six front panel LEDs display AC/DC operational modes, overload status, DC voltage level, shutdown status and system fault status
Set of 4 configuration dipswitches support wet/gel battery charging profiles, adjustable 135/145V high voltage auto transfer during
overvoltages and selectable 75/85/95/105V AC low voltage auto transfer during brownouts
Resettable 8A charger AC input breaker and resettable 12A AC output breaker and automatic 2 speed cooling fan protect the inverter from
load and temperature related failures
Grounding lug properly connects the inverter/charger system to earth ground or vehicle grounding system
Automatic overload and thermal shutoff safely turns off inverter as excessive loads or overheating conditions develop
Front panel remote control connector enables remote off/on switching (requires APSRM4 switch accessory). Optional APSRM4 accessory
also includes user configurable jacks to support inverter shutoff or startup as a vehicle ignition is engaged.
Emergency Home Power
60 Hz
1250
1250
2500
120V
LINE POWER (AC): Maintains 120V nominal sine wave output from line power source. INVERTER POWER (AC):
Maintains PWM sine wave output voltage of 120 V AC (+/-5%).
60 Hz (+/- 0.3 Hz)
Includes 8A input breaker dedicated to the charging system and 12A output breaker for AC output loads
2 AC outlets
DC INPUT: Requires 12VDC input source capable of delivering 125A for the required duration (when used at full
continuous capacity - DC requirements increase during OverPower and DoubleBoost operation). For automotive
applications, professional hardwire installation with 225A minimum battery system fusing is recommended. AC INPUT:
230VAC

Related parts for APS1250