Specifications of SU10000RT3U2TF

Power - Rated
10kVA / 8000W
Ac Outlets
30 (UPS)
Backup Time - Max Load
4 minutes
Voltage - Output Per Connector
208, 120V
Voltage - Input
208V / 44.9A
Ac Input Connector
Hardwire
Connector - Ac Output
2 NEMA L6-30R, 4 NEMA L6-20R and 24 NEMA5-15/20R
Size
25.00" L x 17.50" W x 5.14" H (635.0mm x 444.5mm x 130.6mm)
Weight
57 lbs (25.9kg)
Ac Output Connector
2 NEMA L6-30R, 4 NEMA L6-20R and 24 NEMA5-15/20R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Features
-
Cord Length
-
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
AC mode BTU / hr.
(full load)
AC economy mode
BTU / hr. (full load)
AC economy mode
efficiency rating
(100% load)
Operating Elevation
(ft)
Audible Noise
COMMUNICATIONS
Communications
interface
Network monitoring
port description
PowerAlert software
Communications
cable
WatchDog
compatibility
LINE / BATTERY TRANSFER
Transfer time
Transfer time
(economy mode)
Low voltage transfer
to battery power
(setpoint)
High voltage transfer
to battery power
(setpoint)
SPECIAL FEATURES
Cold Start (startup in
battery mode during
a power failure)
Economy mode
operation
High availability UPS
features
Green & high
efficiency features
CERTIFICATIONS
UPS Certifications
UPS Certification
details
WARRANTY
3415
1275
96%
0-3000m (0 to 10,000 ft.)
60 dBA at front side 1 meter
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports
Included
USB, DB9 serial and EPO cables included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
No transfer time (0 ms.) in online, double-conversion mode
8 ms. typical power failure response in optional economy mode
100V
300V
Cold-start operation supported
Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of
+/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1
millisecond transfer time between modes.
Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
IEC 61000-4-5 1995 B Surge Immunity