SU20K3/3 Tripp Lite, SU20K3/3 Datasheet - Page 5

no-image

SU20K3/3

Manufacturer Part Number
SU20K3/3
Description
UPS SMARTONLINE 20KVA 16KW IGBT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
UPSr
Datasheet

Specifications of SU20K3/3

Power - Rated
20kVA / 1600W
Backup Time - Max Load
5 minutes
Voltage - Output Per Connector
120/208V 3 Phase
Voltage - Input
120 / 208V / 60A per phase (3 phase)
Ac Input Connector
Hardwire
Connector - Ac Output
None (Hardwire)
Size
36.00" L x 19.30" W x 35.30" H ( 914.4mm x 490.2mm x 896.6mm)
Weight
519 lbs (235.4kg)
Ac Output Connector
Hardwire
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Features
-
Cord Length
-
Ac Outlets
-
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
UPS Shipping
dimensions (height
x width x depth /
cm)
Shipping weight
(lbs)
Shipping weight
(kg)
UPS housing
material
Cooling method
ENVIRONMENTAL
Operating
Temperature Range
Storage
Temperature Range
Relative Humidity
COMMUNICATIONS
Communications
interface
Network
monitoring port
description
PowerAlert software
Communications
cable
LINE / BATTERY TRANSFER
Transfer time
Low voltage
transfer to battery
power (setpoint)
High voltage
transfer to battery
power (setpoint)
SPECIAL FEATURES
Cold Start (startup
in battery mode
during a power
failure)
High availability
UPS features
Green & high
efficiency features
CERTIFICATIONS
UPS Certifications
WARRANTY
111.5 x 71.1 x 113
607.2
273.2
Steel
Fans
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
DB9 Serial; Contact closure; Slot for SNMP/Web interface
RS232, contact closure and AS400 monitoring ports are supported by 3 separate DB9 ports
Included
DB9 cabling included
No transfer time (0 ms.) in online, double-conversion mode
Maintains continuous operation during undervoltages as low as 96 / 166V AC (3-Phase, 4-Wire, wye). Below this point,
output is maintained utilizing battery reserves.
Maintains continuous operation during overvoltages as high as 144 / 250V AC (3-Phase, 4-Wire, wye). Above this
point, output is maintained utilizing battery reserves.
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)