SWS600L-48 TDK Corporation, SWS600L-48 Datasheet - Page 15

POWER SUPPLY 48V SGL OUTPUT

SWS600L-48

Manufacturer Part Number
SWS600L-48
Description
POWER SUPPLY 48V SGL OUTPUT
Manufacturer
TDK Corporation
Series
SWSr
Type
Commercialr
Datasheets

Specifications of SWS600L-48

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
600W
Applications
Commercial
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 13A
Size / Dimension
7.48" L x 4.72" W x 2.4" H (190mm x 120mm x 61mm)
Power (watts) - Rated
624W
Operating Temperature
-20°C ~ 74°C
Efficiency
84%
Approvals
CSA, DENAN, EN, IEC, UL
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
13A
Power Rating
624W
Input Voltage
85V AC To 265V AC / 120V DC To 350V DC
Brand/series
SWS Series
Configuration
Enclosed
Output
48 VDC @ 13 A
Power, Output
624 W
Primary Type
AC-DC
Special Features
Parallelable, PFC, Remote On/Off, Remote Sense
Voltage, Input
85 to 265/120 to 350 VAC/VDC
Voltage, Output
48 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1791
Q3860212
SWS600L-48
SWS600L48

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
SWS600L-48
Quantity:
121
・All specifications are subject to change without notice.
SWS
Output voltage external control function is available. Output
voltage can be varied by applying an external voltage (1–6V) to
“PV” terminal and “COM” terminal. Please consider the follow-
ing characteristics.
Note 1. Regarding output voltage adjustment below 20%, please
Output Voltage External Control (PV)
Output - CNT· AUX · ALM : 100VAC 1min. (100mA)
consult our sales.
Nominal
Output
Voltage
Nominal
Output
Voltage
Power Supply
120%
110%
600L, 1000L
20%
120%
110%
20%
0
AC(L)
AC(N)
0
Output Voltage Linearity
Output Voltage Derating
PV voltage (Nominal Input Voltage)
COM
1V
+Vm
-Vm
Connection method
+S
PV
-S
CNT1
CNT2
COM
Load Current
TOG
+Vm
ALM
AUX
-Vm
PC
+S
PV
G1
G2
-S
+
-
External voltage
83% 100%
5V
90%
Withstand
Voltage
Tester
Load
5.5V
6V
Note 2. For 3.3V output model, limit output voltage variation range
For 24V, 48V output model, please meet the following condi-
tions. Reduce peak current value according to output derating
as section 4-2.
Input voltage range : AC170V - 265V
Continuous Peak output time (τ) : Within 10 seconds
Peak output current (Ip) : Within the rated peak output current
Average DC output current (Im) : Within the rated output cur-
rent, Iav
Ip : Peak output current (A)
Iav : Rated output current (A)
Im : Average output current (A)
τ : Peak current pulse width (sec)
T
Auxiliary supply (12V, 0.1A max) is provided to ease customer
application. Aux voltage is functionally isolated from all other
signal terminals and output terminals, and it is always available
as long as input power in the specifi ed voltage range is present.
aA
0A
: Period (sec)
Output Peak Current
Auxiliary Supply
at 30% - 120%. At PV voltage variation 1.5V - 6V.
For 15V output model, limit output voltage variation range
at 20% - 130%. At PV voltage variation 1V - 6.5V.
For 48V output model, limit output voltage variation range
at 20% - 116.7%. At PV voltage variation 1V - 5.8V.
For 60V output model, limit output voltage variation range
at 20% - 110%. At PV voltage variation 1V - 5.5V.
Ip
τ
T
Duty
Duty
Im
=
=
:
up to 35 (%)
( Ip - a ) × τ
τ
T
× 100 (%)
T
Im
+a
15