FPS100048 TDK Corporation, FPS100048 Datasheet - Page 17

PWR SUP FNT END 48V 1008W 21A

FPS100048

Manufacturer Part Number
FPS100048
Description
PWR SUP FNT END 48V 1008W 21A
Manufacturer
TDK Corporation
Series
FPSr
Type
Commercialr
Datasheets

Specifications of FPS100048

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 21A
Size / Dimension
1.61" L x 5" W x 11.4" H (40.9mm x 127mm x 289.6mm)
Power (watts) - Rated
1008W
Operating Temperature
0°C ~ 70°C
Efficiency
88%
Approvals
CE, EN, UL
Line Regulation
0.4%
Load Regulation
0.8%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
21A
Power Rating
1kW
Input Voltage
85V AC To 265V AC / 120V DC To 360V DC
Maximum Output Current
21 A
Maximum Output Power
1008 W
Input Frequency
47 to 63 Hz
Brand/series
FPS1000 Series
Configuration
Enclosed
Operation
Linear
Output
48 VDC @ 21 A
Power, Output
1008 W
Primary Type
AC-DC
Special Features
High Efficiency, Hot Swappable, PFC, Remote On/Off, Remote Sense
Voltage, Input
85 to 265/120 to 360 VAC/VDC
Voltage, Output
48 VDC
Output Current (max)
21A
Screening Level
Commercial
Product Depth (mm)
127mm
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
70C
Mounting Style
Screw
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1239

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
FPS100048/PS
Manufacturer:
TDK-LAMBDA
Quantity:
232
CHAPTER 5 BASIC CONNECTIONS FOR OPERATION
5.1 Connecting single load, Local sensing
Local sensing is suitable for applications where load regulation is not critical. Fig 5-1 shows recommended
load and sensing connections for applications with a single load.
*
5.2 Connecting Single Load, Remote Sensing
Remote sensing is used in cases where the load regulation is important at the load terminals. Use twisted
or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected
to the ground at one point, either the power supply side or the load. The optimal point for the shield ground
should be determined by experimentation. Refer to the power supply specifications for the maximum
voltage drop allowed at the load wires.
5.3 Connecting Multiple loads, radial distribution method
In cases of multiple loads connected to one supply, each load should be connected to the power supply's
output terminals using separate pairs of wires. It is recommended that each pair of wires will be as short
as possible and twisted or shielded to minimize noise pick-up and radiation.
The sense wires should be connected to the power supply output terminals or to the load with the most
critical load regulation requirement.
FPS1000
FPS1000
FPS1000
In Local sense applications, the +/- sense have to be connected to the
+/-V terminals of the FPS1000 units prior the operating the FPS1000 units
Fig 5-1: single load connection, local sensing
Fig 5-2: Remote sensing, single load.
Fig 5-3: Multiple loads connection , radial distribution
SIGNAL
10
SIGNAL
10
SIGNAL
10
RTN
RTN
RTN
OFF
OFF
OFF
ON/
ON/
ON/
7
7
7
+V
+S
+V
+S
+V
+S
-S
-V
-S
-V
-S
-V
1,2,4
3,5,6
13
13
13
1,2,4
3,5,6
1,2,4
8
3,5,6
8
8
Sense lines
Twisted pairs
Load line.
Up to 1V drop.
Load line.
Up to 1V drop.
+
+
-
-
14
LOAD
LOAD
+
+
+
-
-
-
LOAD # 1
LOAD # 2
LOAD # 3

Related parts for FPS100048