ZUP80-2.5/U TDK Corporation, ZUP80-2.5/U Datasheet - Page 21

PWR SUP BENCH PROG 0-80V 200W

ZUP80-2.5/U

Manufacturer Part Number
ZUP80-2.5/U
Description
PWR SUP BENCH PROG 0-80V 200W
Manufacturer
TDK Corporation
Series
ZUPr
Datasheets

Specifications of ZUP80-2.5/U

Voltage - Output
0 ~ 80V
Number Of Outputs
1
Power (watts)
200W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 80 VDC @ 2.5A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
200W
Operating Temperature
0°C ~ 50°C
Efficiency
82%
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.01%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Other names
285-1685
ZUP802.5/U
COM
VCVP
VCCP
RCCP
3.7.4 Single load connection, Remote Sensing
Fig. 3-3: Multiple load connections with distribution terminal
Remote Sensing is used in cases where, in Constant Voltage mode the load regulation is important at
the load terminals. Use twisted or shielded wires to minimize noise pick-up. If shielded wires are used,
the shield should be connected to the ground at one point, either the power supply chassis or the load
ground. The optimal point for the shield ground should be determined by experimentation. At Remote
Sensing, the maximum voltage drop allowed at the load wires is 0.5V per wire for 6V to 60V models and
2V per wire for 80V and 120V models.
COM
VCVP
VCCP
RCCP
3.7.5 Multiple load connections, radial distribution method
In cases of multiple loads connected to one supply, each load should be connected to the power
supply’s output terminals using separate pairs of wires. It is recommended that each pair of wires will be
as short as possible and twisted or shielded to minimize noise pick-up and radiation. The sense wires
should be connected to the power supply output terminals or to the load with the most critical load
regulation requirement.
- S
+S
Fig. 3-2: Remote Sensing, single load.
- S
+S
P
P
EXTERNAL CONTROL
EXTERNAL CONTROL
(ZUP rear panel view)
(ZUP rear panel view)
CONNECTOR
CONNECTOR
2
2
1
1
On/Off
Output Good
VRFV
VRFI
RCVP
On/Off
Output Good
VRFV
VRFI
RCVP
- LS
+LS
- LS
+LS
To Load Terminals
SUPPLY
POWER
SUPPLY
POWER
- LS
+LS
- V
- S
+S
+V
+ V
+ S
- V
- S
Shield
+
_
+
+
+
_
_
_
LOAD #1
LOAD #2
LOAD #3
LOAD

Related parts for ZUP80-2.5/U