2938581 Phoenix Contact, 2938581 Datasheet - Page 3

PWR SUPPLY 5A 100-240AC 24DC

2938581

Manufacturer Part Number
2938581
Description
PWR SUPPLY 5A 100-240AC 24DC
Manufacturer
Phoenix Contact
Series
Quintr
Type
Industrialr
Datasheets

Specifications of 2938581

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
14W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 5A
Size / Dimension
4.92" L x 2.17" W x 5.12" H (125mm x 55mm x 130mm)
Power (watts) - Rated
14W
Operating Temperature
-25°C ~ 70°C
Efficiency
86%
Approvals
ABS, CB, cUL, DNV, GL, GOST, UL
Output Current (max)
5A
Input Voltage
85 to 264V
Output Voltage
24V
Input Frequency
45 to 65Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
-25C
Operating Temperature Max Deg. C
70C
Product
Switching
Commercial/medical
Commercial
Output Power Rating
120 W
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
5 A
Mounting Style
DIN Rail
Brand/series
QUINT-PS
Configuration
Enclosed
Current, Rating
5 A
Frequency
45 to 65 Hz
Height
130 mm
Operation
Switching
Output
24 VDC @ 5 A
Phoenix Part Number
QUINT-PS-100-240AC/24DC/5
Power, Output
14 W
Primary Type
AC-DC
Temperature, Operating, Maximum
70 °C
Temperature, Operating, Minimum
-25 °C
Voltage, Input
85 to 264/90 to 350 VAC/VDC
Voltage, Output
24 VDC
Voltage, Rating
85 to 264 VAC
Width
55 mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Compliant
Other names
1938581
277-1661
QUINT-PS-100-240AC/24DC/ 5
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2938581
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Weight
Operating voltage display
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Mounting position
Assembly instructions
Electromagnetic compatibility
Emitted interference
Immunity to interference
Standard – Electrical equipment of machines
Standard - Safety of transformers
Standard - Electrical safety
Shipbuilding approval
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
Standard – Safety extra-low voltage
Standard - Safe isolation
Standard – Protection against electric shock
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
Standard – Limitation of mains harmonic currents
Standard – Equipment safety
Certificate
Order No.: 2938581
0.83 kg
LED green
> 89 %
4 kV AC (type test)
2 kV AC (routine test)
IP20
I, with PE connection
> 500 000 h in acc. with IEC 61709 (SN 29500)
-25 °C ... 70 °C (> 60 °C derating)
-40 °C ... 85 °C
95 % (at 25 °C, no condensation)
Horizontal DIN rail NS 35, EN 60715
Can be aligned: Horizontal 0 cm, vertical 5 cm
Conformance with EMC directive 89/336/EEC
EN 50081-2
EN 61000-6-2:2005
EN 60204
EN 61558-2-17
EN 60950/VDE 0805 (SELV)
EN 61558-2-17
German Lloyd, ABS
EN 50178/VDE 0160 (PELV)
EN 60950 (SELV)
EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN 57100-410
DIN VDE 0106-101
EN 61000-3-2
GS (tested safety)
CB Scheme
Mar 25, 2010