2866763 Phoenix Contact, 2866763 Datasheet - Page 2

POWER SUPPLY 10A 85-264AC 24DC

2866763

Manufacturer Part Number
2866763
Description
POWER SUPPLY 10A 85-264AC 24DC
Manufacturer
Phoenix Contact
Series
Quintr
Type
Industrialr
Datasheets

Specifications of 2866763

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
240W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 10A
Size / Dimension
4.92" L x 2.36" W x 5.12" H (125mm x 60mm x 130mm)
Power (watts) - Rated
240W
Operating Temperature
-25°C ~ 70°C
Efficiency
92.5%
Approvals
ABS, BV, CB, CSA, cUL, DNV, GL, LR, NK, UL
Product
Switching
Commercial/medical
Commercial
Output Power Rating
240 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Brand/series
QUINT-PS
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 10 A
Phoenix Part Number
QUINT-PS/1AC/24DC/10
Power, Output
18 W
Primary Type
AC-DC
Voltage, Input
85 - 264/90 - 350 VAC/VDC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-1994
QUINT-PS/ 1AC/24DC/10
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866763
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Technical data
Input data
Nominal input voltage
AC input voltage range
DC input voltage range
Short-term input voltage
AC frequency range
DC frequency range
Current consumption
Inrush surge current
Power failure bypass
Input fuse
Permissible backup fuse
Additional text
Type of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Magnetic fuse tripping
Derating
Connection in parallel
Connection in series
Control deviation
Order No.: 2866763
100 V AC ... 240 V AC
85 V AC ... 264 V AC
90 V DC ... 350 V DC
300 V AC
45 Hz ... 65 Hz
0 Hz
Approx. 2.8 A (120 V AC)
Approx. 1.2 A (230 V AC)
< 15 A (typical)
> 40 ms (120 V AC)
> 40 ms (230 V AC)
6.3 A (slow-blow, internal)
B10
B16
AC: 1 x circuit breaker - recommended fuse
Transient surge protection
Varistor
24 V DC ±1%
18 V DC ... 29.5 V DC (> 24 V constant capacity)
10 A (-25°C ... 60°C, U
15 A (with POWER BOOST, -25°C ... 40°C permanently, U
24 V DC)
60 A (SFB technology, 12 ms)
15 A (U
B6
C4
60 °C ... 70 °C (2.5%/K)
Yes, for redundancy and increased capacity
Yes
< 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
In
≥ 100 V AC)
OUT
= 24 V DC)
Jun 12, 2011
Page 2 / 7
OUT
=

Related parts for 2866763