2938646 Phoenix Contact, 2938646 Datasheet - Page 2

POWR SUPPLY 40A 3X400-500AC 24DC

2938646

Manufacturer Part Number
2938646
Description
POWR SUPPLY 40A 3X400-500AC 24DC
Manufacturer
Phoenix Contact
Series
Quintr
Type
Industrialr
Datasheets

Specifications of 2938646

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
960W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
400 ~ 500VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 40A
Size / Dimension
4.92" L x 9.45" W x 5.12" H (125mm x 240mm x 130mm)
Power (watts) - Rated
960W
Operating Temperature
-25°C ~ 70°C
Efficiency
91%
Approvals
ABS, CB, cUL, DNV, GL, GOST, UL
Product
Switching
Commercial/medical
Commercial
Output Power Rating
960 W
Input Voltage
3 x 400 VAC to 500 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
40 A
Mounting Style
DIN Rail
Brand/series
QUINT-PS
Configuration
Enclosed
Current, Rating
40 A
Frequency
45 to 65 Hz
Height
130 mm
Operation
Switching
Output
24 VDC @ 40 A
Phoenix Part Number
QUINT-PS-3X400-500AC/24DC/40
Power, Output
80 W
Primary Type
AC-DC
Temperature, Operating, Maximum
+70 °C (Ambient)
Temperature, Operating, Minimum
-25 °C (Ambient)
Voltage, Input
320 to 575/450 to 800 VAC/VDC
Voltage, Output
24 VDC
Voltage, Rating
320 to 575 VAC
Width
240 mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-1919
QUINT-PS-3X400-500AC/24DC/40
QUINT-PS-3X400-500AC/24DC/40
products is rounded off by power supplies for use in the Ex zone 2, uninterruptible solutions, AS-i power supplies and a
Quint diode.
PHOENIX CONTACT Inc., USA
Technical data
Input data
Nominal input voltage
AC input voltage range
DC input voltage range
AC frequency range
DC frequency range
Current consumption
Nominal power consumption
Inrush surge current
Power failure bypass
Recommended backup fuse
Name of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Connection in parallel
Connection in series
Max. capacitive load
Current limitation
Control deviation
Residual ripple
Peak switching voltages nominal load
Maximum power dissipation idling
Order No.: 2938646
3 x 400 V AC ... 500 V AC
3 x 320 V AC ... 575 V AC (for all three phases)
450 V DC ... 800 V DC
45 Hz ... 65 Hz
0 Hz
Approx. 3x 1.9 A (400 V AC)
Approx. 3x 1.7 A (480 V AC)
960 W
< 15 A (typical)
> 20 ms (400 V AC)
> 20 ms (480 V AC)
3 x 6 A
10 A
16 A (characteristic B)
Transient surge protection
Varistor
24 V DC ±1%
22.5 V ... 28.5 V (> 24 V constant capacity)
40 A (-25°C ... 70°C)
45 A (with POWER BOOST, -25°C ... 40°C permanent)
Yes, for redundancy and increased capacity
Yes
Unlimited
Approx. I
< 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
< 10 mVPP (with nominal values)
< 60 mVPP (20 MHz)
14 W
BOOST
= 45 A (for short circuit)
Page 2 / 7