S8PE-F24024CD Omron, S8PE-F24024CD Datasheet - Page 3

no-image

S8PE-F24024CD

Manufacturer Part Number
S8PE-F24024CD
Description
POWER SUPPLY 10A 3-PHASE
Manufacturer
Omron
Series
S8PEr
Datasheet

Specifications of S8PE-F24024CD

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
240W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
400 ~ 480VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 10A
Size / Dimension
5.51" L x 1.97" W x 6.69" H (140mm x 50mm x 170mm)
Power (watts) - Rated
240W
Operating Temperature
-10°C ~ 60°C
Efficiency
88%
Approvals
CE, CSA, IEC, EN, UL
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Other names
S8PEF24024CD
Engineering Data
I Definition of Inrush Current, Start up Time and Hold Time
I Overload Protction
The Power supply is provided with an overload protec tion function
that protect the load and the power sup ply from possible damage by
over current. When the output current rises above between 105 to
130% of the rated current, the protection function is triggered,
decreasing the output voltage. When output current falls within the
rated range, the overload protection function is automatically cleared.
I De-rating Curve
For UL and CSA the maximum temperature is 50% (with derating of
2%/°C from 40 °C to 50 °C, only for 40 A model)
Output
voltage
AC input
voltage
AC input
current
Ambient temperature (°C)
Input ON
Inrush current input application
Start up time
Three phase input switch mode Power Supply
90%
I Overvoltage Protction
If output voltage exceed the rated voltage more than 20% (50% at
maximum) by some reason, then the output voltage will be turned
OFF automatically for safety. To restart the S8PE, turn OFF the input
voltage, wait for about one minute, then apply the input power again.
(except for 40 A model)
Input OFF
Hold time
96.5%