S82Y-TS01 Omron, S82Y-TS01 Datasheet - Page 9

no-image

S82Y-TS01

Manufacturer Part Number
S82Y-TS01
Description
BATTERY TRAY FOR S8TS
Manufacturer
Omron
Series
S8TSr
Datasheets

Specifications of S82Y-TS01

Accessory Type
Battery Holder Kit
For Use With/related Products
S8T-DCBU-01
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YTS01
■ Inrush Current, Startup Time,
AC input
current
AC input
voltage
Output
voltage
Hold Time
Input ON
Inrush current on input application
Startup time
(1,000 ms max.)
90%
Hold time (20 ms min.)
Input OFF
96.5%
■ Undervoltage Indicator and
When a drop in the output voltage is detected, the red indicator (DC
LOW) lights and transistor (DC LOW: OUT) output turns ON to
provide external notification of the error. The detection voltage is set
to approximately 80% (75% to 90%) of the rated output voltage.
Note: 1. This function monitors the voltage at the power output
Undervoltage Detection Output
Green lit:
Red lit:
Green not lit:
Green lit:
Red not lit:
Red not lit:
Undervoltage Detection Output
2. Transistor output: Open collector
3. The indicators become dimmer as the output voltage
Status of indicator
Blocks with Screw Terminals
30 VDC max., 50 mA max.
ON residual voltage: 2 V max.
OFF leakage current: 0.1 mA max.
approaches 0 V.
terminals. For accurate confirmation of the output status,
measure the voltage at the output terminal.
DC LOW OUT
DC ON
DC LOW
ODC ON
DC LOW
DC ON
DC LOW
−V
(See
note 3.)
+V
Approx. 80%
min. of the rated
output voltage
Approx. 80%
max. of the rated
output voltage
Close to 0 V
Voltage status
Blocks with Connector
Terminals
DC LOW OUT
−V
+V
ON
OFF
OFF
(See note 2.)
S8TS
Output
status
9