S8T-DCBU-02 Omron, S8T-DCBU-02 Datasheet
![no-image](/images/manufacturer_photos/0/4/494/omron_sml.jpg)
S8T-DCBU-02
Specifications of S8T-DCBU-02
Related parts for S8T-DCBU-02
S8T-DCBU-02 Summary of contents
Page 1
... S8T-BUS03 Bus Line Connector (Order separately.) S8T-DCBU-02 Output voltage Output current 2.5 A Number of Connectors 1 Connector 10 Connectors (See note.) Connection via Wiring Connect to AC lines. Connect to AC lines. Load CSM_S8T-DCBU-02_DS_E_4_1 S8T-DCBU-02 S8TS Model number S8T-DCBU-02 Model number S8T-BUS03 S8T-BUS13 Load 1 ...
Page 2
... Refer to Backup Time on page 10 for details. 3. Refer to Functions on page 7 for details the number of S8T-DCBU-02 Buffer Blocks to be connected is “N,” set the detection current × Specified by S8TS-06024@ connection sure to mount an End Plate (PFP-M: Order separately) on each end of the Buffer Block. Refer to DIN Rails on page 15. ...
Page 3
... Note: 1. The backup current must be less than 5 A (parallel operation connection is required if the backup current exceeds 2.5 A) and the Buffer Block must be fully charged. If three or more S8T-DCBU-02 Buffer Blocks are used in parallel operation and the backup current exceeds 5 A, the momentary power failure time that can be compensated for will be reduced. ...
Page 4
... Power Supply To Be Connected The power consumption of the S8T-DCBU-02 is approximately make sure that the output capacity of the connected Power Supply is sufficient. If the S8T-DCBU-02 is connected to a previously installed power supply, the voltage may drop due to the power supply's overload protection, or backup operations may not be possible. ...
Page 5
... Connecting to the S8TS-06024@ When connecting one or more S8T-DCBU-02 Blocks to the S8TS-06024@ using Bus Line Connectors, connect them to either the left or right end of the Blocks. Heat dissipation will be interfered with if the S8T-DCBU-02 Blocks are not connected to the end. Correct Correct S8T-DCBU-02 S8T-DCBU-02 ...
Page 6
... AC input. Use this procedure for periodic inspection as well. 1. Turn ON the AC power of the connected power supply. 2. Check the READY indicator on the S8T-DCBU-02 to confirm that it is lit. READY Indicator READY output relay ...
Page 7
... The overcurrent protection circuit of the connected power supply has operated. Note: The contact capacity of the output relay is 0 VDC. Backup Operation The S8T-DCBU-02 will switch to the backup operation if a voltage drop is detected on the connected power supply. BACKUP Indicator BACKUP output relay ...
Page 8
... F: BACKUP Indicator (BACKUP: Red Slider Bus Line Connector S8T-BUS03 A: Selector B: Bus Line Connector terminal Bus Line Connector Terminal (+ Bus Line Terminal (− Protective Earthing Terminal ( J: I/O Terminal (−V) K: I/O Terminal (+V) L: Rail Stopper M: Connecting part of Bus Line Connector N: Terminal Cover S8T-DCBU- ...
Page 9
... I/O terminal voltage Output current of the S8T-DCBU-02 open READY output closed READY indicator BACKUP output open closed BACKUP indicator Power supply output hold time open closed 2 seconds (typical) open closed S8T-DCBU-02 open closed open closed Power supply restart time Backup time 9 ...
Page 10
... If the input voltage increases, the output voltage for the backup operation will also increase, reducing the backup time due to the higher power consumption of the load. Parallel Operation with 2 Blocks 2.0 2.5 Parallel Operation with 4 Blocks 6.0 7.5 S8T-DCBU-02 10 Vin = 24 V typical Vin = 24 V guaranteed 1 0.1 0.0 1.0 2 ...
Page 11
... W (approximately 10 W per Block) from the S8TS-06024@ *4 110 W reduces the total output capacity when more than one S8TS-06024@ Block is connected The rated output current of the S8T-DCBU-02 is 2.5 A per *6 170 W Block regardless of the number of S8TS-06024@ Basic *7 152 W Blocks that are connected. *8 ...
Page 12
... S8T-DCBU-02 Load current Output hold time (ms) (A) 100 VAC 200 VAC 1.5 133 144 4 5 2.5 190 200 5 100 105 7.5 68 ...
Page 13
... S8T-DCBU-02 Momentary power failure time: 1,000 ms 200 VAC 100 VAC 200 VAC 345 290 6.2 5 576 196 496 300 380 155 512 308 390 157 ...
Page 14
... Note: All units are in millimeters unless otherwise indicated. ■ Buffer Block and Bus Line Connector Buffer Block S8T-DCBU-02 Six, M4 with 10 square washer (Sliding: 15 max.) Bus Line Connector S8T-BUS03 24 2.5 18 105 2.5 120 80.7 120 5.6 8 7.6 5.5 5 Sliding 13 70 5.5 2 Sliding 4 35 S8T-DCBU- ...
Page 15
... Mounting Rails (Material: Aluminum) PFP-100N PFP-50N 4.5 PFP-100N2 4.5 End Plate PFP (5 1,000 (500)* * Values in parentheses are for the PFP-50N. ±0 1,000 10 6.2 1.8 Eight, M4 pan-head screw 1 50 35.5 35.3 1.8 11.5 10 1.3 4.8 M4 spring washer S8T-DCBU-02 7.3 ± 0. ± 0.3 ± 0. 29.2 1 1.5 15 ...
Page 16
... Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the specified mounting method only. Ensure sufficient heat dissipation when installing the Product to increase its long-term reliability. Natural cooling is used, so mount the S8T-DCBU-02 so that there is airflow around it. S8TS-06024 ...
Page 17
... The S8T-DCBU-02 will perform the backup operation not only for momentary power failures or voltage drops, but also when the input power is OFF. The backup time is particularly long for light loads. Check the devices connected to the S8T-DCBU- sure it has stopped operation correctly. Periodic Inspection and Periodic Replacement The S8T-DCBU-02 contains built-in electrolytic capacitors, which have a limited life ...
Page 18
... Troubleshooting The following table lists the errors that may occur when the S8T-DCBU-02 is used, along with their probable causes and remedies. Check the relevant items. When Cause During installation The S8TS-06024@ and S8T-DCBU-02 cannot be connected. When checking The S8TS-06024@ when operation ...
Page 19
... The voltage output from the S8T-DCBU-02 dur- ing the backup operation may be lower because overcurrent protection has operated in the S8T-DCBU-02. The input voltage to the S8T-DCBU-02 may less. A voltage of approximately higher may be input to the I/O terminals of the S8T-DCBU-02, causing the overvoltage protec- tion circuit to operate ...
Page 20
... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...