IRPLDIM2U International Rectifier, IRPLDIM2U Datasheet - Page 8

no-image

IRPLDIM2U

Manufacturer Part Number
IRPLDIM2U
Description
BALLAST DIM DIG 32W/T8 120VAC
Manufacturer
International Rectifier
Datasheet

Specifications of IRPLDIM2U

Main Purpose
Lighting, Ballast Control
Utilized Ic / Part
IR21592
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Secondary Attributes
-
Embedded
-
Primary Attributes
-
Lead Free Status / Rohs Status
Not Compliant
Other names
*IRPLDIM2U
Isolation and the Signals for DALI
The Digitally Addressable Lighting Interface is optically isolated from the microcontroller. Fig. 7 shows the connec-
tions between DALI and microcontroller.
The two wires from the DALI are converted to four signals. Two of the four are the transmit signal (RB2) and
receive signal (RX_DALI). The other two signals are the communications-enable (RB0) signal and the receive-
drive (RB1) signal. The transmit signal and the receive signal directly correlate to the levels seen on the Digitally
Addressable Lighting Interface. For receiving higher voltage logic on the DALI is translated to 5 volt logic at the
micro controller, and for transmission, the 5 volt logic is translated to the higher voltage logic on the DALI.
The ballast achieves very low power by controlling the communications circuit with the communication-enable
signal and the receive-drive signal. During normal operation the PIC16F628 enables the communication circuitry
with the communication-enable signal. With this signal there is enough current, less than 100uA, to indicate when
data is being sent to the ballast, but not enough current to accurately transfer the data. Upon detection (done by
a S/H built into the PIC16F628) the receive-drive is asserted to raise the current above 500uA to achieve good
signal transfer across the isolation. The receive-drive signal is only enabled long enough to transfer all the data;
then it is disabled (see waveforms in figure 8). This method strongly reduces the power/current use. The com-
parator built into the PIC16F628 is used to set the threshold for detection of the incoming data. The signal RA2 is
used as threshold for the comparator.
8
DALI
-
+
Fig. 7 DALI and Micro Controller connections
RB0
RB2
RB1
RA1
RA2
MICRO-CONTROLLER
RECEIVE-DRIVE
TX_DALI
ENABLE
RX_DALI
IRPLDIM2U
www.irf.com

Related parts for IRPLDIM2U