G32A-A20-VD DC5-24 Omron, G32A-A20-VD DC5-24 Datasheet - Page 5

REPLACEMENT POWER CARTRIDGE 20A

G32A-A20-VD DC5-24

Manufacturer Part Number
G32A-A20-VD DC5-24
Description
REPLACEMENT POWER CARTRIDGE 20A
Manufacturer
Omron
Series
G3PAr
Datasheet

Specifications of G32A-A20-VD DC5-24

Accessory Type
Power Device Cartridge
Control Voltage Range
19 VAC to 264 VAC
Load Voltage Rating
264 V
Load Current Rating
20 A
Relay Type
Solid State
For Use With/related Products
G3PA Series
For Use With
G3PA-220B-VDDC5-24 - RELAY SSR SPST 20A 24VDC DIN MT
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Color
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G32A-A20-VDDC5-24
G32AA20VDDC524
G32AA20VDDC524NC
G3PA
Operation
■ Replacement Parts
G32A-A Power Device Cartridge
The G32A-A Power Device Cartridge (a Triac Unit) can be replaced with a new one. When the temperature indicator has changed from pink to red,
the triac circuitry may have malfunctioned possibly by an excessive flow of current, in which case, dismount the damaged cartridge for replacement.
The damaged cartridge can be replaced with a new one without disconnecting the wires from the G3PA.
Improve the heat radiation efficiency of the G3PA before replacing the cartridge.
The G32A-A Power Device Cartridge can withstand an excessive current for a short period of time, such as may be caused accidentally by the
short circuitry of the load, in which case the temperature indicator will not turn red.
Be sure to turn OFF the power supply when replacing the Cartridge. Supplying power with the Cartridge removed may result in malfunction.
Appearance
G32A-A10(L)-VD G32A-A20(L)-VD
G32A-A40(L)-VD
G32A-A60(L)-VD
G32A-A420-VD(-2)
G32A-A430-VD(-2)
G32A-A450-VD-2
Replacing Power Device Cartridges
When replacing Power Device Cartridges, use the specified model. Using a Power Device Cartridge other than the specified one will result in faulty
operation and destruction of the elements.
5