MKS1XT-10 DC12 Omron, MKS1XT-10 DC12 Datasheet - Page 9

RELAY PWR DC SPST-NO 10A 12VDC

MKS1XT-10 DC12

Manufacturer Part Number
MKS1XT-10 DC12
Description
RELAY PWR DC SPST-NO 10A 12VDC
Manufacturer
Omron
Series
MK-S(X)r
Datasheet

Specifications of MKS1XT-10 DC12

Relay Type
General Purpose
Coil Type
Standard
Contact Form
SPST-NO (1 Form A)
Contact Rating (current)
10A
Switching Voltage
220VDC - Max
Coil Current
126mA
Coil Voltage
12VDC
Turn On Voltage (max)
9.6 VDC
Turn Off Voltage (min)
1.8 VDC
Mounting Type
Socket
Termination Style
Socketable
Circuit
SPST-NO (1 Form A)
Contact Rating @ Voltage
10A @ 220VDC
Control On Voltage (max)
9.6 VDC
Control Off Voltage (min)
1.8 VDC
Coil Voltage Vdc Nom
12V
Contact Current Max
10A
Contact Voltage Dc Nom
220V
Coil Resistance
95ohm
Contact Configuration
SPST-NO
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
MKS1XT10DC12
Z2956
Safety Precautions
Be sure to read the precautions and information common to all electromechanical relays, contained in the Technical User’s Guide,
“Electromechanical Relays, Technical Information” for correct use.
Precautions for Correct Use
Installation
• Models for DC loads (i.e., models with “X” in the model number)
• Models for AC loads do not contain a permanent magnet.
• When mounting a P7MF-06(-D) Front-mounting Socket to a DIN
Gang Mounting
Conditions for mounting multiple MKS-X relays on the same DIN rail.
* Gang mounting of the Front-Mounting Sockets is not possible if the
Wiring
• The contact terminals on Models for DC Loads (i.e., models with “X” in
• Be sure to check plarity when wiring DC coil MKS-X relays with
Models for
DC Loads
Models for
AC Loads
contact carry current exceeds 10A.Provide space on both the right
and left sides of the Sockets.
The mounting pitch is given in the following diagram.
have permanent magnets built into the insulating block. If a
permanent magnet or other magnetic body comes near the Relay,
magnetic interference will occur with the built-in permanent magnet
and the contact switching capacity will be decreased.
Track, attach PFP-M End Plates on both sides of the Socket to
prevent it from moving.
the model number) have polarity. Wiring with incorrect polarity may
result in inability to turn OFF the Relay or loss of functionality.
built-in operation indicators.
Relay
20
15
10
5
0
0
10
10A
15A
Rated current
of Relay
20
Mounting interval (mm)
30
Mounting interval
Back-Connecting
40
Socket
50
Socket
Front-Connecting
Socket
*
General Purpose Power Relays
Operating Environment
Do not use the Relay in environments with combustible gas. Doing so
may result in explosion due to arcing.
Storage
Models for DC Loads (i.e., models with “X” in the model number) are
magnetized because they have a built-in magnet to deflect and
extinguish the arc. Do not install the Relay near IC cards or other
items that may be adversely affected by magnetism.
Usage
Use the Relay mounted in the P7M-06P or P7MF-06(-D) Socket.
Test Button
• Turn OFF the power supply before operating the test button. Always
• Do not use the test button as a switch.
• The durability of the test button is 100 operations minimum.
The circuit can be checked using either of two modes.
Test Button Applications
Example: Checking operation of Relays and sequence circuits.
return the test button to the original position after you use it.
(No tool is required.)
Press the button
Test Button
DC specification: Blue
AC specification: Red
for operation.
(momentary)
Mode 1
MKS-X
pressing down on the
Lock the contacts by
button and turning it.
(locked)
Mode 2
Normal
9