MM4KP DC24 Omron, MM4KP DC24 Datasheet - Page 13

no-image

MM4KP DC24

Manufacturer Part Number
MM4KP DC24
Description
RELAY POWER 4PDT 5A 24VDC
Manufacturer
Omron
Series
MMKr
Datasheet

Specifications of MM4KP DC24

Relay Type
General Purpose
Contact Form
4PDT (4 Form C)
Contact Rating (current)
5A
Switching Voltage
250VAC, 250VDC - Max
Coil Type
Latching, Dual Coil
Coil Current
113mA
Coil Voltage
24VDC
Turn On Voltage (max)
19.2 VDC
Mounting Type
Socket
Termination Style
14 Pin Socketable
Circuit
4PDT (4 Form C)
Contact Rating @ Voltage
5A @ 220VAC
Control On Voltage (max)
19.2 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Control Off Voltage (min)
-
Lead Free Status / Rohs Status
 Details
Other names
MM4KPDC24
MM4KPDC24NC
Safety Precautions
Refer to Safety Precautions for All Relays.
■ Mounting
Make sure that the Relay is free from iron powder or iron core,
otherwise the iron dust may adhere to the Relay. As a result the
movable contact may not operate properly.
An arc may be generated between the contacts in switching
operation. Be sure to keep combustible objects away from the Relay.
If the arc will have a bad effect around the Relay, the use of a model
with a casing is recommended.
A model switching DC load incorporates an insulation base with a
small built-in permanent magnet. Be sure to keep magnets or ferrous
objects away from the permanent magnet, otherwise the capacity of
the maximum switching current may drop.
The PL Back-connecting Socket must be flush-mounted from the
surface of the panel.
If two or more Relays are mounted together, make sure that a
minimum space of 20 mm is provided between adjacent Relays.
Be sure to mount the Relay so that the movable contact is in the
downward direction.
■ Connection
• When connecting a load to the contact terminals of a model for
• Use proper crimp terminals or 1.2- to 2-mm-dia. single-conductor
Screw Terminal Model
Do not bend the coil terminals, otherwise the coil wire may be dis-
connected. Make sure that the tightening torque applied to each ter-
minal is 1.27 N • m and the insertion force is 49 N for 10 s.
Solder Terminal Model
Make sure that Relay terminals are free of flux or other foreign sub-
stance before soldering the Relay terminals. Finish soldering the
Relay terminals quickly, otherwise the coil wire may be broken.
switching DC loads (“X” models), consider the polarity of the con-
tact terminals so that the generated arcs on the adjacent poles will
not collide. (For example, if the common connections of the Relay
are all positive or all negative, no arc collision will occur.)
wire to connect screw terminals.
MMK
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
20 mm
min.
MMK
Normal mounting direction
In the interest of product improvement, specifications are subject to change without notice.
■ Circuits
• You cannot use single contact to demagnetize the set coil as shown
• NC contacts can remain open for a few milliseconds when the reset
• Do not allow voltage to be applied simultaneously to both the set
• There is no reason to apply voltage to Latching Relays continu-
• A model for DC loads incorporates a permanent magnetic for arc
• Arcing when switching DC power can cause nitric gas to be
below.
coil turns ON and OFF. NO contact can remain open for a few milli-
seconds when the set coil turns ON and OFF while the Relay is
latched. Design your circuits to allow for this.
and reset coil. If voltage is applied simultaneously, the Relay will be
set.
ously because they will latch properly with a single pulse of suffi-
cient width. Continuously applying voltage will only waste power.
suppression. Keep floppy disks away from the Relay, otherwise the
data on the floppy disk may be damaged.
generated. The case of the MM@XKP contains holes to allow the
gas to escape. This, however, makes it possible for dust and dirt to
enter the case. Be sure to use the MM@XKP in a suitable
environment.
Latching Relay coil
NC contact of the Relay
MMK contact
(NC)
The contact
may fail to
hold itself.
Relay coil
Load
MMK
13