G3NA-210B-AC100-120 Omron, G3NA-210B-AC100-120 Datasheet - Page 4

RELAY SSR 120VAC@10A ZERO AC IN

G3NA-210B-AC100-120

Manufacturer Part Number
G3NA-210B-AC100-120
Description
RELAY SSR 120VAC@10A ZERO AC IN
Manufacturer
Omron
Series
G3NAr

Specifications of G3NA-210B-AC100-120

Control Voltage Range
100 VAC to 120 VAC
Load Current
10A
Circuit
SPST-NO (1 Form A)
Output Type
AC, Zero Cross
Voltage - Input
100 ~ 120VAC
Voltage - Load
19 ~ 264 V
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Package / Case
Hockey Puck
Load Voltage Rating
240 V
Off State Leakage Current (max)
5 mA, 10 mA
Load Current Rating
10 A
Contact Form
1 Form A
Output Device
Triac
Input To Output Isolation Method
Photocoupler
Relay Type
General Purpose Hockey Puck
Operating Voltage Range
19VAC To 264VAC
Isolation Voltage
2500VAC
Control Voltage Type
AC
Relay Terminals
Screw
Load Voltage Min
24VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3NA210BAC100120
Z919
Dimensions
■ Relays
Note: All units are in millimeters unless otherwise indicated.
■ Optional Accessories (Order Separately)
One-touch Mounting Plate
The One-touch Mounting Plate is used to mount the G3NA to a DIN
Track.
R99-12 FOR G3NA (for the G3NA and G3NE)
470
G3NA-610B, G3NA-625B
G3NA-650B
Solid State Relays (600 VAC Models)
Two, M4 mounting
holes for the G3NE
58 max.
58 max.
Two, M5 x 12 screws
Two, M5 x 12 screws
47.5
47.5
12±0.4
12±0.4
44
44
30
44
Two, M4 mounting
holes for the G3NA
43 max.
43 max.
25
25
4.5
4.5
8.2
8.2
4.5 dia.
4.5 dia.
Two, M4 x 2
screws
Two, M4 x 2
screws
Operating
indicator
Operating
indicator
G3NA-6
• When a Relay is mounted to DIN Track, use it within the rating for a
• Use the following DIN Tracks: PFP-100N or PFP-100N2.
To mount the Relay to DIN
Track, first mount it to the
One-touch Mounting Plate
and then attach it to the DIN
Track as shown in the
diagram.
To remove the Relay from
the DIN Track, pull down on
the tab with a screwdriver in
the direction of the arrow.
28 max.
28 max.
26 max.
Relay without a heat sink.
26 max.
16.8
16.8
47.6
47.6
Mounting Holes
Mounting Holes
± 0.2
± 0.2
Two, 4.3-dia.
or M4 holes
Two, 4.3-dia.
or M4 holes
Terminal Arrangement/
Internal Connections
(Top View)
Terminal Arrangement/
Internal Connections
(Top View)
(−)
(−)
1
4
1
4
Output
Output
Input
Input
Load
Load
(+)
(+)
2
3
2
3
Load
power
supply
Load
power
supply

Related parts for G3NA-210B-AC100-120