H3YN-41 AC100-120 Omron, H3YN-41 AC100-120 Datasheet - Page 11

RELAY TIMER ANALOG 4PDT 0-10HRS

H3YN-41 AC100-120

Manufacturer Part Number
H3YN-41 AC100-120
Description
RELAY TIMER ANALOG 4PDT 0-10HRS
Manufacturer
Omron
Series
H3YNr
Datasheets

Specifications of H3YN-41 AC100-120

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
4PDT (4 Form C)
Delay Time
0.1 Min ~ 10 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
3A @ 250VAC
Voltage - Supply
100 ~ 120VAC
Mounting Type
Socket
Termination Style
Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Timing Range
0.1 min to 10 Hrs
Supply Voltage
100 V to 120 V
Rohs Compliant
Yes
Contact Configuration
4PDT
Timing Adjustment
DIP Switch
Relay Mounting
Plug In
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption, Lead free / RoHS Compliant
Other names
H3YN-41 AC100-240
H3YN41AC100120
H3YN41AC100240
Z1137
H3YN
Precautions
When using the H3YN in any place where the ambient
temperature is more than 50°C, supply 90% to 110% of the rated
voltages (at 12 VDC: 95% to 110%).
Do not leave the H3YN in time-up condition for a long period of
time (for example, more than one month in any place where the
ambient temperature is high), otherwise the internal parts may
become damaged. Therefore, the use of the H3YN with a relay
as shown in the following circuit diagram is recommended.
The H3YN must be disconnected from the socket when setting
the DIP switch, otherwise the user may touch a terminal imposed
with a high voltage and get an electric shock.
Do not connect the H3YN as shown in the following circuit
diagram on the right hand side, otherwise the H3YN’s internal
contacts different from each other in polarity may become
short-circuited.
Use the following safety circuit when building a self-holding circuit
with the H3YN and an auxiliary relay, such as an MY Relay, in
combination.
In the case of the above circuit, the H3YN will be in pulse operation.
Correct
C at . N o. G C T MC N 1
1-800-55-OMRON
OMRON ELECTRONICS LLC
One East Commerce Drive
Schaumburg, IL 60173
CORRECT USE
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
Incorrect
: H3YN
R
3/ 02
H3YN
MY Relay
MY Relay
OMRON ON- -LINE
Global - - http://www.omron.com
USA - - http://www.omron.com/oei
Canada - - http://www.omron.com/oci
S pec if ic at ions s ubjec t t o c hange w it hout not ic e.
11
Do not set to the minimum setting in the repeat-cycle modes, or
the contact may become damaged.
Be careful not to apply any voltage to the terminal screws on the
back of the timer. Mount the product so that the screws will not
come in contact with the panel or metal parts.
Do not use the H3YN in places where there is excessive dust,
corrosive gas, or direct sunlight.
Do not mount more than one H3YN closely together, otherwise
the internal parts may become damaged. Make sure that there is
a space of 5 mm or more between any adjacent H3YN Models.
The internal parts may become damaged if a supply voltage
other than the rated ones is imposed on the H3YN.
The H3YN as a built-in timer conforms to VDE 0435/P2021
provided that the following conditions are satisfied.
Handling
Do not touch the DIP switch while power is supplied to the H3YN.
Before dismounting the H3YN from the socket, make sure that no
voltage is imposed on any terminal of the H3YN.
Wiring
The power supply for the H3YN must be protected with
equipment such as a breaker approved by VDE.
Only a load with basic isolation can be connected to the output
contact. The H3YN is a model with basic isolation. Therefore, the
H3YN and the load will ensure reinforced isolation, thus meeting
VDE standards.
Insulation requirement: Overvoltage category II,
pollution degree 2 (with a clearance of 1.5 mm and a creepage
distance of 2.5 mm at 240 VAC)
There must be no difference in polarity between any output
terminals next to each other of the H3YN-4 or H3YN-41,
H3YN-4Z, H3YN-41-Z.
PRECAUTIONS FOR VDE CONFORMANCE
OMRON CANADA, INC.
416-286-6465
885 Milner Avenue
Scarborough, Ontario M1B 5V8
P r int ed in U . S . A .
H3YN