H5CX-A AC100-240 Omron, H5CX-A AC100-240 Datasheet - Page 40

RELAY TIMER DIGITAL SPDT 100/240

H5CX-A AC100-240

Manufacturer Part Number
H5CX-A AC100-240
Description
RELAY TIMER DIGITAL SPDT 100/240
Manufacturer
Omron
Series
H5CXr
Datasheets

Specifications of H5CX-A AC100-240

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.001 Sec ~ 9999 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC
Mounting Type
Panel Mount
Termination Style
Screw Terminal
Timing Adjustment Method
DIP Switches
Timing Initiate Method
Input Voltage, Trigger Signal
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Other names
H5CX-A-AC100-240
H5CXAAC100240
Z1645
■ Terminal Arrangement
Note 1. Do not connect unused terminals as relay terminals.
■ Input Circuits
Signal, Reset, and Gate Input
No-voltage Input (NPN Inputs)
2. The power supply and input circuit are not isolated.
3. Terminals 1 and 6 are connected internally.
4. Terminals 7 and 10 have the same reset function. The same function will be performed whichever terminal is connected. Terminals 7 and
5. Recommended lead wires: AWG18 to AWG24 (cross-sectional area: 0.205 to 0.823 mm
10 are not connected internally, however, so do not use them for cross-over wiring.
or aluminum.
IN
Input use 0 V
1 kΩ
(−)
Unused
11
6
1
+14 V
7
2
Internal
circuit
(+)
12
8
3
OUT2
9
4
10
13
5
OUT1
Voltage Inputs (PNP Inputs)
IN
Approx. 4.7 kΩ
2
), single line or twisted-pair cable, made of copper
Internal
circuit
H5CX-B
40