XDP4/I(400V50HZ) MOELLER, XDP4/I(400V50HZ) Datasheet - Page 3

STARTER, DOL, ISOLATOR, PLASTIC

XDP4/I(400V50HZ)

Manufacturer Part Number
XDP4/I(400V50HZ)
Description
STARTER, DOL, ISOLATOR, PLASTIC
Manufacturer
MOELLER
Datasheet

Specifications of XDP4/I(400V50HZ)

Supply Voltage Range
400V
No. Of Phases
Three
Power Rating
4kW
Current Rating
8.5A
Svhc
No SVHC (18-Jun-2010)
Contact Voltage Ac Nom
400VAC
External Depth
160mm
External Length / Height
222mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
This Motor Starter is not fitted with an Overload Relay at the factory, and therefore the control circuit is not complete. Once an Overload
Relay has been installed, the factory cable tails should be terminated according to the appropriate diagram below.
Applicable to:
XD(P)4
XD(P)5.5
XD(P)7.5
XDR(P)4
XDR(P)5.5
XDR(P)7.5
XSD(P)5.5
XSD(P)7.5
XSD(P)11
All Overload Relays have an adjustment dial (yellow in colour) marked with the range of motor full load current that can be
accommodated by that particular size of relay. The dial should be turned so that the full load current of the motor (obtained from the
motor rating label) lines up with the pointer below the dial. Note that for star-delta motor starters (XSD…), where the overload is
connected in the motor supply cables, the dial should be set to 0.58 x FLC see table below.
The Overload Relay is supplied set to manual reset operation (H). To obtain automatic reset operation (A), depress and rotate the
Hand/Auto plunger (blue in colour) anti-clockwise to the ‘A’ position. The ‘A’ position should not be used with 2-wire control.
XD(P)5.5 / XDR(P)5.5
XD(P)7.5 / XDR(P)7.5
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
XD(P)4 / XDR(P)4
Starter Type
XSD(P)5.5
XSD(P)7.5
XSD(P)11
XSD(P)15
XD(P)11
Starter Rating
0.37kW
0.55kW
0.75kW
1.1kW
1.5kW
2.2kW
5.5kW
7.5kW
5.5kW
7.5kW
11kW
11kW
15kW
3kW
4kW
Final Control Cable Connections to Overload Relay
Selection and Setting of Overload Relay
Typical FLC @400V
11.3A
15.2A
21.7A
11.3A
15.2A
21.7A
29.3A
1.1A
1.5A
1.9A
2.6A
3.6A
6.6A
8.5A
5A
Applicable to:
XD(P)11
XSD(P)15
Overload Relay
ZB12-1,6
ZB12-1,6
ZB12-2,4
ZB12-10
ZB12-10
ZB12-12
ZB12-16
ZB32-24
ZB12-10
ZB12-10
ZB12-16
ZB32-24
ZB12-4
ZB12-4
ZB12-6
Setting Range
1.6-2.4A
10-16A
16-24A
10-16A
16-24A
1-1.6A
1-1.6A
2.4-4A
2.4-4A
6-10A
6-10A
9-12A
6-10A
6-10A
4-6A
Typical Setting
11.3A
15.2A
21.7A
12.6A
1.1A
1.5A
1.9A
2.6A
3.6A
6.6A
8.5A
6.6A
8.8A
17A
5A