S701D03N3S EATON CUTLER HAMMER, S701D03N3S Datasheet - Page 30

Motor Starter

S701D03N3S

Manufacturer Part Number
S701D03N3S
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of S701D03N3S

No. Of Phases
Three
Power Rating
1.1kW
Current Rating
3.5A
Peak Reflow Compatible (260 C)
No
Output Current
3.5A
Supply Voltage Max
415VAC
Control Voltage Max
415V
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39.2
Operation
Overload Functionality
Overtemperature
Protects the device from
overheating. Starter will
shut down at 100°C.
Stall
Selectable protective feature,
unit trips to protect system in
event motor can not get to
rated speed in the defined
ramp period.
Starting Characteristics
Kick Start
Provides an initial boost of
current to the motor to help
break free the rotor and start
spinning the motor.
Starting Characteristics—Kick Start
Ramp Start
The most commonly used
form of soft start. This allows
you to set the initial torque
value (of the ramp) and then
raises it to full voltage
conditions.
Starting Characteristics—Ramp Start
30
100%
100%
Start
Kick
Torque
Initial
Control Products Catalog CA08102001E—September 2010 www.eaton.com
Reduced Voltage Motor Starters
Solid-State Starters
Ramp
Jam
Selectable protective feature,
unit trips to prevent damage
to motor during normal run.
Phase Loss
Selectable protective feature,
trips under voltage loss
condition to any phase.
Phase Reversal
Selectable protective feature,
trips when phase rotation is
something other than A-B-C.
0–85% of locked rotor
torque
0–2.0 seconds duration
Adjustable initial torque =
0–85% of locked
rotor torque
Adjustable ramp time =
0.5–180 seconds (can be
extended with factory
modification)
Time (Seconds)
Time (Seconds)
Run (FLA)
Run (FLA)
Kick Start
Selectable feature that
provides a current “kick”
of up to 550% of full load
current for 0 to 2.0 seconds.
This provides the additional
torque required at startup to
break free a motor.
Ramp Start
Provides a constant increase
in torque to the motor.
Current Limit Start
Limits the maximum current
available to the motor during
the startup phase.
Soft Stop
Allows for a controlled
stopping of a frictional load.
Shorted SCR Detection
Monitors for shorted SCR
in the power polls.

Related parts for S701D03N3S