Solid State Relays 3A/50VAC SPST-NO

70S2-04-D-03-V

Manufacturer Part Number
70S2-04-D-03-V
Description
Solid State Relays 3A/50VAC SPST-NO
Manufacturer
Magnecraft / Schneider Electric
Datasheets

Specifications of 70S2-04-D-03-V

Control Voltage Range
3 VDC to 32 VDC
Load Voltage Rating
24 V
Load Current Rating
3 A
Contact Form
SPST - NO
Mounting Style
PCB
Relay Type
Solid State
Termination Style
Solder Leads
Control Voltage Type
DC
Input Voltage
3VDC To 32VDC
Contact Configuration
SPST-NO
Load Current
3A
Load Voltage Range
8VAC To 50VAC
Switching Mode
Zero Cross
Relay Terminals
Through Hole
Brand/series
70S2 Series
Current, Rating
3 A
Current, Surge
60 A Peak @ +25°C
Dielectric Strength
3750 V (RMS)
Dimensions
1.7 in. L x 0.4 in. W x 1 in. H
Function
Zero-Switching
Mounting Type
PCB
Number Of Pins
4
Standards
UL, CSA, TUV
Temperature, Ambient, Maximum
100 °C
Temperature, Ambient, Minimum
-40 °C
Termination
Solder
Voltage, Control
32 VDC
Voltage, Rating
50 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
4/30
General Specifications (@ 25° C)
Output Characteristics
Number and type of Contacts
Switching Device
Current Rating
Switching voltage
Switching Type
Maximum Rate of Rise Off State Voltage (dv/dt)
Min. Load current to maintain on
Non-Repetitive Surge Current (1 cycle)
Max. Off state leakage current (rms)
Typical On State Voltage Drop (rms)
Minimum Peak Blocking Voltage
Input Characteristics
Voltage Range
Must Release Voltage
Typical Input Current @ 5VDC or 240VAC
Max. Reverse Control Voltage
Performance Characteristics
Operating time (response time)
Dielectric strength
Environment
Product certifications
Ambient air temperature
around the device
Miscellaneous Characteristics
Thermal Resistance (Junction to Case)
Weight
File No. E258297
UL Recognized
70S2 Series Solid State Relays/3, 5 Amp, V Style
Input
Terminals
Board Mounting
On
Off
Terminals to Chassis
Input to Output
Standard version
Storage
Operation
Printed Circuit
(UL 508)
°C/W
g (oz)
Units
V/us
mA
mA
mA
ms
ms
°C
°C
A
A
V
V
V
V
V
V
V
V
8….50 AC
3….32 DC
-40…+125
-40…+100
70S2-04-D
Zero Cross
60 / 300
4000 AC
4000 AC
SPST-NO
UR, CSA
25 (0.9)
75 / 50
200 AC
1.6 AC
3 / 10
1….19
3 / 5
1 DC
3 DC
Triac
300
8.3
8.3
0.5
Output Terminals
Integrated Thermal
Management
8….50 AC
6….32 DC
-40…+125
-40…+100
70S2-05-D
Zero Cross
4000 AC
4000 AC
SPST-NO
UR, CSA
25 (0.9)
200 AC
1.6 AC
1….6
1 DC
3 DC
Triac
300
8.3
8.3
0.5
75
60
3
3
M agne cr aft S olu tion Guide 1 0 5 A
24….140 AC
-40…+125
-40…+100
3….32 DC
70S2-04-B
Zero Cross
60 / 300
4000 AC
4000 AC
SPST-NO
UR, CSA
75 / 50
25 (0.9)
400 AC
1.6 AC
1….19
6 / 10
3 / 5
1 DC
3 DC
Triac
300
8.3
8.3
0.5