CQM1-SF200 Omron, CQM1-SF200 Datasheet

no-image

CQM1-SF200

Manufacturer Part Number
CQM1-SF200
Description
CQM1 SAFETY RELAY MODULE
Manufacturer
Omron
Datasheets

Specifications of CQM1-SF200

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
CQM1/CS1W-SF200
Same Dimensions as a Typical
I/O Module but Requires Less
Installation Space and Less Wiring than
Conventional Safety Relay Units
H
H
H
H
Ordering Information
J I/O MODULE TYPE EMERGENCY-STOP UNIT
J MODEL NUMBER LEGEND
CQM1: CQM1 I/O Module Type
CS1W: CS1 I/O Module Type
1.
2.
CQM1-jjjjj
CS1W-jjjjj
Main contact
DPST-NO
Safety Relay PLC Module
Safety Relay Module functions as an
I/O Module for OMRON’s CQM1H and CS1
Series PLCs
Requires less installation space and wiring
Monitors power supply, output, and internal
relays for safety circuits
Equipped with four general-purpose input
terminals
SF: I/O Module Type Emergency-Stop Unit
Contact Configuration (Safety Output)
2:
Function
DPST-NO
1
1
2 3
2 3
Rated voltage
24 VDC
4
4
Auxiliary contact
None
2
Number of input
channels
1 channel or
2 h
2 channels possible
3.
4.
Contact Configuration (OFF-Delay Output)
0:
Contact Configuration (Auxiliary Output)
0:
l
None
None
ibl
Number of
general-purpose
inputs
4 inputs
Do Not Remove
p
Part number
CQM1-SF200
CS1W-SF200

Related parts for CQM1-SF200

CQM1-SF200 Summary of contents

Page 1

... SF: I/O Module Type Emergency-Stop Unit 2. Contact Configuration (Safety Output) 2: DPST-NO Auxiliary contact Number of input channels None 1 channel channels possible l ibl 3. Contact Configuration (OFF-Delay Output) 0: None 4. Contact Configuration (Auxiliary Output) 0: None 2 Do Not Remove Number of Part number general-purpose inputs 4 inputs p CQM1-SF200 CS1W-SF200 ...

Page 2

... CQM1-SF200 Item Resistive load (cos φ =1) Rated load 250 VAC Rated carry current GENERAL-PURPOSE INPUT BLOCK Item CQM1-SF200 Power supply voltage 24 VDC Operating voltage range 85% to 110% of rated power supply voltage Input impedance 4.0 kΩ Input current 6 mA (typical VDC Must-operate voltage/current 14 ...

Page 3

... CQM1/CS1W-SF200 J CHARACTERISTICS Item CQM1-SF200 Contact resistance (See Note 1) 100 mΩ Operating time 300 ms max. (not including bounce time) Response time (See Note max. (not including bounce time) Insulation resistance (See Note 3) Between safety circuits and safety output: 20 MΩ min. (at 500 VDC) Between general-purpose inputs and safety output: 20 MΩ ...

Page 4

... Application Examples J TWO CHANNELS OF EMERGENCY STOP SWITCH INPUT (COMMON TO CQM1-SF200 AND CS1W-SF200) PLC output Timing Chart Emergency stop switch S1 Reset switch S2 K3 (NC) K3 (NO) K1 and K2 (NC) K1 and K2 (NO) KM1 and KM2 (NC) KM1 and KM2 (NO) PLC input PLC output KM3 CQM1/CS1W-SF200 PLC ...

Page 5

... CQM1/CS1W-SF200 J TWO CHANNELS OF LIMIT SWITCH INPUT (COMMON TO CQM1-SF200 AND CS1W-SF200) PLC output Timing Chart Limit switches S1 and S2 Reset switch S3 K3 (NC) K3 (NO) K1 and K2 (NC) K1 and K2 (NO) KM1 and KM2 (NC) KM1 and KM2 (NO) PLC input PLC output KM3 Indicator Indicator Indicator S1: ...

Page 6

... J TWO CHANNELS OF LIMIT SWITCH INPUT WITH AUTO-RESET (COMMON TO CQM1-SF200 AND CS1W-SF200) PLC output Timing Chart Limit switches S1 and S2 (NC) Limit switches S1 and S2 (NO) K3 (NC) K3 (NO) K1 and K2 (NC) K1 and K2 (NO) KM1 and KM2 (NC) KM1 and KM2 (NO) PLC input PLC output KM3 CQM1/CS1W-SF200 ...

Page 7

... CQM1/CS1W-SF200 Dimensions Unit CQM1-SF200 J CS1W-SF200 8 ...

Page 8

... CPU) beginning with word 0000. Note: The 1 to 16-point Modules are allocated 16 bits and 17 to 32-point Modules are allocated 32 bits. For example, 8-point DC Input Modules are allocated bits 00 to 07. CQM1-SF200 is allocated 16 points. Number of slots Power CPU Supply ...

Page 9

... CQM1/CS1W-SF200 Installation J TERMINAL ARRANGEMENT CQM1-SF200 CS1W-SF200 10 ...

Page 10

... Safety circuit block General-purpose input block Note: 1. The NC terminal is incorporated in the CS1W-SF200 only. 2. Values in parentheses are for the CS1W-SF200. J INDICATORS Indicator Color Indicator status RDY Green Lit (CQ (CQM1-SF200 only --- Not lit PWR Green Lit Not lit K1 and K2 Yellow Lit Not lit ...

Page 11

... CQM1/CS1W-SF200 Precautions J WIRING Turn OFF the CQM1-SF200 or CS1W-SF200 before wiring the Module. Do not touch the terminals of the Module while the power is turned ON, because the terminals are charged and may cause an electric shock. Use the following to wire the Module. 2 Stranded wire: 0. Solid wire: 1 ...