CQM1-SF200 Omron, CQM1-SF200 Datasheet - Page 11

no-image

CQM1-SF200

Manufacturer Part Number
CQM1-SF200
Description
CQM1 SAFETY RELAY MODULE
Manufacturer
Omron
Datasheets

Specifications of CQM1-SF200

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
CQM1/CS1W-SF200
Precautions
J WIRING
Turn OFF the CQM1-SF200 or CS1W-SF200 before wiring the
Module. Do not touch the terminals of the Module while the
power is turned ON, because the terminals are charged and may
cause an electric shock.
Use the following to wire the Module.
Stranded wire: 0.75 to 1.5 mm
Solid wire: 1.0 to 1.5 mm
Tighten each screw to a torque of 0.78 to 1.18 N S m, or the
Module may malfunction or generate heat.
External inputs connected to T11 and T12, or T21 and T22 of the
Relay Module must be no-voltage contact inputs.
J EXTERNAL CONNECTIONS
OMRON ELECTRONICS LLC
One Commerce Drive
Schaumburg, IL 60173
847-843-7900
For US technical support or other inquiries:
800-556-6766
Cat. No. GC SAFETY-2
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, divide by 25.4
2
2
2/03
Specifications subject to change without notice
OMRON CANADA, INC.
885 Milner Avenue
Toronto, Ontario M1B 5V8
416-286-6465
J APPLICABLE SAFETY CATEGORY
Safety Relay Modules CQM1-SF200 and CS1W-SF200 meet the
requirements of Safety Category 4 of the EN954-1 Standards
when used as shown in the examples provided by OMRON. The
Relays may not meet the standards in some operating
conditions. The applicable safety category is determined from the
whole safety control system. Make sure that the whole safety
control system meets EN954-1 requirements.
(EN954-1)
OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.omron.com/oei
Canada - http://www.omron.ca
Printed in USA