Specifications of XPSDME1132P

Contact Current Max
8mA
Contact Voltage Dc Nom
24V
Contact Configuration
DPST-NO
Relay Mounting
DIN Rail
External Height
66mm
External Width
114mm
External Depth
45mm
Rohs Compliant
Yes
Description
Illuminated display
Configurable safety controller XPSMCppZp,
with screw connectors
Safety automation system solutions
Preventa™ configurable safety controllers
type XPSMC
1
2
3
4
5
6
7
8
9
10
11
Front cover of controllers:
1
2
3
4
5
6
7
8
Rear face of controllers:
9
(1) Depending on controller model.
Description
Configurable safety controllers XPSMCppZp
LED details
LED
LED display and system diagnostics.
Two LEDs for CANopen or Profibus
SUB-D 9-pin male connector for connection on CANopen bus (XPSMC16ZC/
MC32ZC)
or SUB-D 9-pin female connector for connection on Profibus bus (XPSMC16ZP/
MC32ZP).
Solid-state safety output and “muting” indicator light terminals.
Power supply (c 24 V) and relay safety output terminals.
Control output terminals for power supply to safety inputs and safety input
terminals.
RJ45 connector for connection on Modbus® serial link.
RESET button (resetting of controller).
Mounting plate for mounting on rail.
PWR
CNF
E In
E Ex
COM
R1, R2 Green
RUN
ERR
1…16
1…32
o1…o6 Green
RUN
Color
Green
Yellow
Red
Red
Green
Green
Red
Green
Green
Status
On
On
Flashing
On
On
On
On
Flashing
Off
On
On
Off
Flashing
(x 1)
Flashing
(x 2)
Flashing
(x 3)
On
Flashing
On
Flashing
On
Flashing
Meaning
Supply voltage present.
In configuration mode.
Not configured, initial power-up.
Internal error: all safety outputs deactivated.
External error: all safety outputs associated
with the defective circuit are deactivated.
Controller communicating via the TER (RJ45)
connection.
Relay outputs 13/14, 23/24, 33/34 and 43/44
activated.
Fault on these outputs.
Hardware OK for the Profibus bus or the
CANopen bus.
Communicating on Profibus bus or on
CANopen bus.
Normal status.
Communication impossible, configuration
error, damaged cabling or absence.
Bus deactivated
Communicating on CANopen or Profibus bus.
Normal status.
Warning limit reach.
Control event error on CANopen bus.
Synchronization error on CANopen bus.
Input circuit closed.
Error detected on input relating to LED.
Solid-state output activated.
Short-circuit, anomaly on output.
Run mode.
Changing from run mode to stop mode.
(1)
connection status.