X24640P-1.8 XICOR [Xicor Inc.], X24640P-1.8 Datasheet - Page 7

no-image

X24640P-1.8

Manufacturer Part Number
X24640P-1.8
Description
400KHz 2-Wire Serial E 2 PROM with Block Lock
Manufacturer
XICOR [Xicor Inc.]
Datasheet
X24640
Acknowledge Polling
The maximum write cycle time can be significantly
reduced using Acknowledge Polling. To initiate
Acknowledge Polling, the master issues a start condi-
tion followed by the Slave Address Byte for a write or
read operation. If the device is still busy with the
internal write cycle, then no ACK will be returned. If the
device has completed the internal write operation, an
ACK will be returned and the host can then proceed
with the read or write operation. Refer to figure 7.
Figure 7. Acknowledge Polling Sequence
BYTE LOAD COMPLETED
COMMAND SEQUENCE
ENTER ACK POLLING
CONTINUE NORMAL
CYCLE COMPLETE.
BY ISSUING STOP.
(READ OR WRITE)
READ OR WRITE
ADDRESS BYTE
ISSUE SLAVE
RETURNED?
SEQUENCE?
CONTINUE
PROCEED
VOLTAGE
ISSUE
START
HIGH
ACK
YES
YES
NO
NO
ISSUE STOP
ISSUE STOP
7038 FM 09
7
Figure 8. Current Address Read Sequence
READ OPERATIONS
Read operations are initiated in the same manner as
write operations with the exception that the R/W bit of
the Slave Address Byte is set to one. There are three
basic read operations: Current Address Reads,
Random Reads, and Sequential Reads.
Current Address Read
Internally, the device contains an address counter that
maintains the address of the last word read or written
incremented by one. After a read operation from the
last address in the array, the counter will “roll over” to
the first address in the array. After a write operation to
the last address in a given page, the counter will “roll
over” to the first address on the same page.
Upon receipt of the Slave Address Byte with the R/W
bit set to one, the device issues an acknowledge and
then transmits the eight bits of the Data Byte. The
master terminates the read operation when it does not
respond with an acknowledge during the ninth clock
and then issues a stop condition. Refer to figure 8 for
the
sequence.
It should be noted that the ninth clock cycle of the read
operation is not a “don’t care.” To terminate a read
operation, the master must either issue a stop condi-
tion during the ninth cycle or hold SDA HIGH during
the ninth clock cycle and then issue a stop condition.
SIGNALS
FROM THE
MASTER
SDA BUS
SIGNALS
FROM THE
SLAVE
address,
S
A
R
S
T
T
acknowledge,
1
0 1 0
ADDRESS
SLAVE
1
A
C
K
and
DATA
data
7038 FM 10
transfer
O
S
T
P
P

Related parts for X24640P-1.8