E1IM10AACL10 TELE, E1IM10AACL10 Datasheet

no-image

E1IM10AACL10

Manufacturer Part Number
E1IM10AACL10
Description
CURRENT MONITORING 1-PHASE
Manufacturer
TELE
Series
ENYAr
Datasheet

Specifications of E1IM10AACL10

Contact Configuration
SPCO
Power Consumption
5VA
Supply Voltage Max
230VAC
Contact Current Max
5A
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Contact Current Ac Max
5A
Contact
RoHS Compliant
Monitoring relays - ENYA series
Multifunction
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
AC current monitoring in 1-phase mains with adjustable threshold,
hysteresis and tripping delay.
2. Time ranges
Start-up suppression time (Start): -
Tripping delay (Delay):
3. Indicators
Green LED ON/OFF:
Red LED ON/OFF:
Red LED flashes:
Yellow LED ON/OFF:
4. Mechanical design
Self extinguishing plastic housing, IP rating IP40
Mounted on DIN rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
5. Input circuit
Supply voltage:
Terminals:
Tolerance:
Rated consumption:
Rated frequency:
Duration of operation:
Reset time:
Wave form:
Hold-up time:
Drop-out voltage:
Overvoltage category:
Rated surge voltage:
OVER
UNDER
WIN
OVER+Latch
UNDER+Latch Undercurrent monitoring with fault latch
WIN+Latch
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
AC current monitoring in 1-phase mains
Overcurrent monitoring
Undercurrent monitoring
Monitoring the window between Min and Max
Overcurrent monitoring with fault latch
Monitoring the window between
Min and Max with fault latch
indication of supply voltage
indication of failure of the
corresponding threshold
indication of tripping delay of the
corresponding threshold
indication of output relay
230V AC
Li-N
-15% to +15% of UN
5VA (0.8W)
AC 48 to 63Hz
100%
500ms
Sinus
-
>20% of rated voltage
III (in accordance with IEC 60664-1)
4kV
Adjustment range
0,1 to 10s
www.tele-online.com
6. Output circuit
1 potential free change over contact
Rated voltage:
Switching capacity:
Fusing:
Mechanical life:
Electrical life:
Switching frequency:
Overvoltage category:
Rated surge voltage:
7. Measuring circuit
Measuring variable:
Measuring input:
Terminals:
Overload capacity:
Starting current:
Input resistance:
Switching threshold US:
Hysteresis H:
Overvoltage category:
Rated surge voltage:
8. Accuracy
Base accuracy:
Adjustment accuracy:
Repetition accuracy:
Voltage influence:
Temperature influence:
9. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
10. Weight
Single packing:
Package of 10pcs:
1s
3s
250V AC
1250VA (5A / 250V)
5A fast acting
20 x 10
2 x 10
at 1000VA resistive load
max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
III (in accordance with IEC 60664-1)
4kV
AC sinus, 48 to 63Hz
10A AC
Li, Lk
13A (ex 10A - distance > 5mm)
100A
50A
3mW
see table ordering information or
printing on the unit
see table ordering information or
printing on the unit
III (in accordance with IEC 60664-1)
4kV
≤5% of nominal value
±5% of nominal value
≤2% of nominal value
-
≤0,05% / °C
-25 to +55°C
-25 to +70°C
-25 to +70°C
15% to 85%
(in accordance with IEC 60721-3-3
class 3K3)
2, if built in 3
(according to IEC 664-1)
72g
655g per package
5
6
operations
operations
E1IM10AACL10

Related parts for E1IM10AACL10

E1IM10AACL10 Summary of contents

Page 1

... Voltage influence: Temperature influence: 9. Ambient conditions Ambient temperature: Storage temperature: Transport temperature: Relative humidity: Pollution degree: 10. Weight Single packing: Package of 10pcs: www.tele-online.com E1IM10AACL10 250V AC 1250VA (5A / 250V) 5A fast acting operations operations 5 at 1000VA resistive load max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1) ...

Page 2

... The output relay R switches into on-position again, if the current exceeds the Max-value. UNDER+Latch: The output relay R switches only into on-position again by interrupting and re-applying of the supply voltage, provided that the measured current is beyond the Min-value. Latch latch activated latch activated www.tele-online.com E1IM10AACL10 latch activated ...

Page 3

... Connections Ordering information Types Rated voltage U N E1IM10AACL10 230V RELEASE 2009/07 Subject to alterations and errors Dimensions Functions Switching threshold Max 10% to 100 O+L, U+L, W+L Min www.tele-online.com E1IM10AACL10 5mm 44mm 60mm Delay Hysteresis 0,1 to 10s adjustable 17,5mm Part. No. 1340200 ...