ACF-3000DM-A Amprobe, ACF-3000DM-A Datasheet - Page 2

Current Transducer

ACF-3000DM-A

Manufacturer Part Number
ACF-3000DM-A
Description
Current Transducer
Manufacturer
Amprobe
Datasheets

Specifications of ACF-3000DM-A

Current Measuring Range Ac
300A To 3000A
Accuracy
± 1%
Accuracy %
1%
Rohs Compliant
NA
For Use With
DM-II And DMII Pro
Lead Free Status / RoHS Status
na
A M P R O B E
F
L E X I B L E
Current Ranges
Output Sensitivity (AC coupled)
Load Impedance
Accuracy (at +25ºC)
Linearity (10% to 100% of range)
Noise
Frequency Range
Phase Error
Position Sensitivity (with cable > 25mm from the coupling)
External Field (with cable > 200mm from the head)
Power Supply
Low battery indication
External power
Gain variation
Common mode voltage
Working Voltage (see Safety Standards section)
Head Cable Colour..............................................................: Yellow
Head Cable Length (double insulated)..............................: 24 inches (610mm)
Head Cable Diameter.....................................................: 0.562 inches (14.3 mm)
Head Bend Radius ..............................................................: 1.5 inches (38.1 mm)
Cable Length (head to electronics) ..................................: 78.7 inches (2 meters)
Output Connection ..............................................................: Hypotronics D01EEB306FST
Operating Temperature Range .................:-4 to 194º F (-20 to +90º C) head
................................................................ -4 to 185º F (-20 to +85º C) electronics
Storage Temperature Range............. -40 to 221º F (-40 to +105º C) head
..................................................................: -4 to 185º F (-20 to +85º C) electronics
Operating Humidity.............................................: 15% to 85% (non condensing)
Weight.............................................................:0.40 Lb (180 g) head,
The ACF-3000 SR is an AC current probe utilising the Rogowski principle. It can be used to measure currents up to
3000A.
* Specifications subject to change without notice
Safety Standards
BSEN61010-1: 1993, 600V Cat III, Pol. Deg 2
Use of the probe on uninsulated conductors is limited to 600 V ACRMS or DC and frequencies below 1 kHz.
EMC Standards
EN 61326 : 1998
C
®
U R R E N T
MODEL ACF-3000 SR
General Characteristics
Electrical Characteristics
Safety Standards
T
R A N S D U C E R
Phone:954-499-5400
www.amprobe.com
Fax:954-499-5454
Miramar, FL
3000 A ACRMS
0.333 mV per A
100 kOhm minimum
± 1% of range (45 – 65 Hz)
± 0.2% of reading
0.3 mV AC
10 Hz to 5 kHz (- 3 dB)
< ± 1º (45 – 65Hz), ± 10º (at 5 kHz)
2 x AAMN 1500 LR6 alkaline 4000 hours, 3000 hrs typical
Red LED
Battery eliminator, via 2.1mm connector, 3V DC: Socket type A16M500
± 0.08% of reading per 1.8º F (1º C)
Voltage between Output and Earth must not exceed 30V
600 V ACRMS or DC
± 2% of range
± 1% of range
RMS

Related parts for ACF-3000DM-A