T30UIPB BANNER ENGINEERING, T30UIPB Datasheet - Page 5

Ultrasonic Sensor

T30UIPB

Manufacturer Part Number
T30UIPB
Description
Ultrasonic Sensor
Manufacturer
BANNER ENGINEERING
Datasheet

Specifications of T30UIPB

Sensing Range Min
300mm
Sensing Range Max
2m
Switching Frequency
128kHz
External Diameter
40mm
Operating Temperature Range
-20°C To +70°C
Peak Reflow Compatible (260 C)
No
Output Type
Transistor
Contact Rating
20mA
Leaded Process Compatible
No
Figure 3.
10
20
4
0
NOTE: The analog current output tracks
Banner Engineering Corp.
www.bannerengineering.com • Tel: 763.544.3164
Window
Window
slightly past each window limit
(from 3.8 to 20.5 mA).
Near
Near
Output current as a function of
target position
Voltage-Sourcing Models
Current-Sourcing Models
Target Position
Target Position
Positive
Positive
Slope
Slope
Minneapolis, MN U.S.A.
U-GAGE
Window
Window
Far
Far
NOTE: All LED indicators momentarily go OFF when sensor changes state between
Signal LED
The red Signal LED indicates the strength and condition of the sensor’s incoming
signal.
Output LEDs
Each yellow Output LED lights when a target is sensed within the programmed window
limits.
Power ON/OFF LED
The green Power ON/OFF LED indicates the operating status of the sensor.
The U-GAGE T30 Series sensor may be programmed for either a positive or a negative
output slope, based on which condition is taught first (see Figure 3). If the near limit is
taught first, the slope will be positive; if the far limit is taught first, the slope will be
negative. Banner’s scalable analog output automatically distributes the output signal over
the width of the programmed sensing window.
The U-GAGE T30 also features a 2-second hold upon loss of the analog signal, which is
useful for harsh and unstable applications. In the event of analog signal loss for longer
than 2 seconds, the analog output goes to 3.6 mA or 0V dc, which may be used to trigger
an alarm.
In the unlikely event of a microprocessor memory error, all of the LEDs will flash in
sequence. If this occurs, the setup parameters have been lost and the sensor may be
corrupt. Contact your Banner representative for further information.
RUN Mode
Analog Output
Self-Diagnostic Error Mode
Power ON/OFF LED
T30 Series with Analog and Discrete Outputs
Signal LED Status
PROGRAM and RUN modes.
ON Solid
Flashing
Flashing
OFF
OFF
No signal is received, or the target is beyond the range limitations
of the sensor (with some tolerance beyond the recommended
minimum and maximum sensing distance)
Relative received signal strength
Power is OFF (or in PROGRAM mode, if other LEDs are ON)
Sensor is operating normally (power is ON, RUN mode)
Discrete output is overloaded (RUN mode)
Indicates
Indicates
P/N 57438 Rev. C
5