G3PE-215B DC12-24 Omron, G3PE-215B DC12-24 Datasheet - Page 9

no-image

G3PE-215B DC12-24

Manufacturer Part Number
G3PE-215B DC12-24
Description
15A 1-phase SSR, Zero Cross
Manufacturer
Omron
Datasheet

Specifications of G3PE-215B DC12-24

Control Voltage Range
12 VDC to 24 VDC
Load Voltage Rating
240 V
Load Current Rating
15 A
Output Device
Triac
Mounting Style
DIN Rail
Relay Type
Solid State
Termination Style
DIN Rail
Control Voltage Type
AC
Load Current
15A
Relay Terminals
Screw
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Relationship between the G3PE and Ducts or Other
Objects Blocking Airflow
If the depth direction of
the G3PE is obstructed by
ducts, the heat radiation
will be adversely affected.
Ventilation Outside the Control Panel
Note: 1. If the air inlet or air outlet has a filter, clean the filter regularly
G3PE Ambient Temperature
15A and 25A models have ambient temperature of 40°C, while 35A
and 45A models have 25°C ambient Temperature. The G3PE uses a
semiconductor to switch the load. This causes the temperature inside
the control panel to increase due to heating resulting from the flow of
electrical current through the load. The G3PE reliability can be
increased by adding a ventilation fan to the control panel to dispel
this heat, thus lowering the ambient temperature of the G3PE.
(Arrhenius's law suggests that life expectancy is doubled by each
10°C reduction in ambient temperature.)
Example: For 10 G3PE SSRs with load currents of 15 A,
Note: 1. Size of fans: 92 mm × 92 mm, Air volume: 0.7 m
SSR rated current (A)
Required number of
fans per SSR
Incorrect Example
Duct or other object
blocking airflow
2. Do not locate any objects around the air inlet or air outlet,
3. A heat exchanger, if used, should be located in front of the
2. If there are other instruments that generate heat in the
3. Ambient temperature: The temperature that will allow the
SSR
to prevent it from clogging to ensure an efficient flow of air.
otherwise the objects may obstruct the proper ventilation of
the control panel.
G3PE to ensure the efficiency of the heat exchanger.
Ambient temperature of control panel: 30°C
control panel in addition to SSRs, more ventilation will be re-
quired.
SSR to cool by convection or other means.
SSR
Air inlet
0.23 × 10 = 2.3
Thus, 3 fans would be required.
Duct
Duct or other object blocking airflow
Vertical
Direction
Use ducts that have a
shallow depth, to provide
a sufficient ventilation
area.
Countermeasure 1
Be aware of airflow
50 mm max.
Duct
15 A
0.23
Duct
(No more
than 1/2
the SSR
depth is
recom-
mended.)
SSR
25 A
0.39
SSR
If the ducts cannot be made
lower, place the G3PE on a
metal base so that it is not
surrounded by the ducts.
Countermeasure 2
Base
35 A
0.54
Ventilation
outlet
(Axial Fan)
Duct
Duct
3
/min,
Airflow
45 A
0.70
Single-phase Solid State Relays for Heaters
SSR
SSR
G3PE
435