CS1W-AD081-V1 Omron, CS1W-AD081-V1 Datasheet - Page 12

no-image

CS1W-AD081-V1

Manufacturer Part Number
CS1W-AD081-V1
Description
MODULE, ANALOG IN, 8CH
Manufacturer
Omron
Datasheet

Specifications of CS1W-AD081-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Function Blocks (Unit Ver. 3.0)
System Common Blocks
Control Blocks
Note: High-speed control of function blocks is supported (the operation cycle can be set to 0.01 s, 0.02 s, or 0.05 s), except when using the
External Controller Blocks
Note: LCB05D not supported.
Operation Blocks
System
Controller
External Controller
Block
Alarm/ Signal restric-
tions/Hold
Function Blocks (Unit Ver. 3.0)
LCB05D.
Type
Type
Type
Type
System Common
2-position ON/OFF
(See note.)
3-position ON/OFF
(See note.)
Basic PID (See note.)
Advanced PID (See note.) Performs PID with two degrees of freedom control for enabling deviation/MV compensation,
Blended PID
Batch Flowrate Capture
Fuzzy Logic
Indication and Setting
(See note.)
Indication and Operation
(See note.)
Ratio Setting (See note.)
Indicator (See note.)
ES100X Controller Termi-
nal (See note.)
4-Point Warning Indicator
(See note 3.)
High/Low Alarm
(See note 1.)
Deviation Alarm
(See note 1.)
Rate-of-change Operation
and Alarm (See note 1.)
High/Low Limit
(See note 1.)
Deviation Limit
(See note 1.)
Analog Signal Hold
(See note 1.)
Block Name
Block Name
Block Name
Block Name
2-position type ON/OFF controller
3-position type ON/OFF controller for heating/cooling ON/OFF control
Performs basic PID control.
MV tracking, etc.
Performs PID control on the cumulative value (cumulative deviation) between the accumu-
lated value PV and accumulated value Remote Set Point.
Functions to open the valve at a fixed opening until a fixed batch accumulated value is
reached.
Manual setter with PV indication and SP setting functions
Manual setter with PV indication and MV setting functions
Ratio and bias setter with PV indication and ratio setting function
PV indicator with PV alarm
Performs monitoring and setting for an ES100X Controller connected directly to the RS-
232C port on the Loop Control Unit.
Makes settings common to all function blocks and outputs signals for the system.
Outputs up to two analog outputs based on fuzzy logic performed on up to 8 analog inputs.
Provides the alarm contact outputs for the high/high, high, low, and low/low limits of single
analog signals. This function block provides the same function as the Indicator block (model
034).
Provides the alarm contact outputs for the high and low limits of single analog signals.
Provides the alarm contact outputs for the deviation of two analog signals.
Provides the alarm contact outputs for the high and low limits of rate-of-change operation
when the analog signal rate-of-change is output.
Limits the high and low limits of single analog signals.
Calculates the deviation between two analog signals, and limits the deviation within that
range.
Holds the maximum, minimum or instantaneous value of single analog signals.
Function
Function
Function
Function
System Common Blocks
17

Related parts for CS1W-AD081-V1