Specifications of XTSC001BBA

No. Of Phases
Three
Power Rating
550W
Current Rating
1A
Mounting Type
DIN Rail
Frequency
50Hz
Supply Voltage
110V
Contact Rating
1A
Control Voltage Max
120V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34-116
34
Technical Data and Specifications
Table 34-142. Overload Relay Specifications
Protection
Trip Class
Reset
Indications
PCBA
Options
General
Description
Thermal
Phase Loss
Phase Imbalance
Inrush Current
Class 5, 10, 20, 30
M / M-O
A / A-O
Test Indicator
Trip Indicator
Power Sensing
Instant Reset by Power ON
Thermal memory
Cold and Hot Trip Curves
Power Consumption
Safety Cover
Remote Reset
IEC Contactors & Starters
XT IEC Power Control
Overload Relays — C396
C396_2_
Standard
1.05 x FLA: Does not trip
1.25 x FLA: Overload trip
1 Phase = 0, Trip time = 3s (Hot Status)
Max - Min / Max > 40%,
Trip time = 3s (Hot Status)
> 8 x Max FLA, Trip time is 0.3s (Cold Status)
Manual / Manual + Stop
Auto / Auto + Stop
Auto Reset Time = 165s
Yellow
Yellow
3 phase
CPU reset by Power ON after 2 – 3s
< 3 min.
Power ON > 20 min. is Hot Status
< 300 mW
Covers FLA dial, DIP switches
24V DC, 24V AC, 120V AC, 240V AC
Selectable
For more information visit: www.eaton.com
Overload Relay Specifications (Continued)
Climate Considerations
Voltages
FLA Range
Safety
Capacity
Load Terminal Capacity
Load Terminal Tightening Torque in Nm (lb-in)
General Description
Ambient Temperature
(Operating)
Ambient Temperature
(Storage / Transportation)
Humidity
Altitude (Operating)
Pollution (Operating —
External)
Mechanical Shock
Resistance
(IEC/EN 68-2-17)
Vibration (Lloyd’s Register
of Shipping, Vibration Test
2)
Temperature
Compensation
Control Voltage
Insulation Voltage (Ui) —
Main Circuit
Insulation Voltage (Ui) —
Control Circuit
Impulse Withstand Voltage
(Uimp) VAC
45 mm Frame: C396A_
65 mm Frame: C396B_
110 mm Frame: C396C_
Degree of Protection
Control Terminal Capacity
Control Terminal Tightening
Torque in Nm (lb-in)
45 mm Frame: C396A_
65 mm Frame: C396B_
110 mm Frame: C396C_
45 mm Frame: C396A_
65 mm Frame: C396B_
110 mm Frame: C396C_
Dimensions . . . . . . . . . . . . . . Pages 34-117, 34-118
C396_2_
Standard
-25° to 65°C (-13° to 149°F) inside enclosure
-40° to 80°C (-40° to 176°F)
UL991 (H3): 20 – 95% non-condensing
NEMA ICS1: 2000 meters max above sea
level
Pollution degree 3
15g
Continuous
12 – 690V AC, 50/60 Hz
1000V AC
690V AC
6000
0.1 – 45A
15 – 110A
30 – 150A
IP20 (Stand-Alone Version Only)
18 – 14 AWG
0.79 (7)
14 – 6 AWG
10 – 1 AWG
6 AWG – 250 mcm
3.2 (28)
9.0 (80)
22.6 (200)
6g
CA08102001E
March 2009