XTSC001BBA EATON CUTLER HAMMER, XTSC001BBA Datasheet - Page 125

Motor Starter

XTSC001BBA

Manufacturer Part Number
XTSC001BBA
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTSC001BBA

No. Of Phases
Three
Power Rating
550W
Current Rating
1A
Mounting Type
DIN Rail
Frequency
50Hz
Supply Voltage
110V
Contact Rating
1A
Control Voltage Max
120V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
March 2009
Product Selection
Product Selection for Manual Motor Starter Applications
When ordering, specify Catalog Numbers
according to the following stipulations:
selected based on the overload current
range required for a given motor. This
current range is determined from the
motor Full Load Ampere rating and
Motor Service Factor usually found on
the motor nameplate.
Table 34-145. XTPB Pushbutton Manual Motor Protectors — Global and North American Ratings
Type 1 and Type 2 Coordination
Motor Protective Device with Thermal and Magnetic Trip
Frame B
Notes:
Single-phasing sensitivity to IEC/EN 60947-4-1, VDE 0660 Part 102.
Can be snap-fit to IEC/EN 60715 top-hat (DIN) with 7.5 or 15 mm height.
Service Factor (SF) — Setting I r of current scale in dependence of load factor:
For manual motor protective circuit breaker switching capacity, see Page 34-147.
CA08102001E
Rated
Uninterrupted
Current —
I u = I e (Amps)
10
12
16
20
25
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
Select Manual Motor Protectors by full load amperes. Maximum Motor Ratings (kW, hp) are for reference only.
In this range, calculate motor rating according to rated current. Specified values to NEC 430.6(A)(1).
Manual Motor Protectors are
SF = 1.15 -> I r = 1 x I n mot
SF = 1 -> I r = 0.9 x I n mot
FLA
Adjustment
Range /
Overload
Release —
I r (Amps)
10 – 16
16 – 20
20 – 25
0.1 – 0.16
0.16 – 0.25
0.25 – 0.4
0.4 – 0.63
0.63 – 1
1 – 1.6
1.6 – 2.5
2.5 – 4
4 – 6.3
6.3 – 10
8 – 12
B-Frame
Short
Circuit
Release —
I rm (Amps)
140
168
224
280
350
2.2
3.5
5.6
8.8
14
22
35
56
88
Maximum Motor Ratings
Maximum kW Rating
AC-3 — P (kW)
3-Phase
220 –
240V
0.06
0.09
0.12
0.25
0.37
0.75
1.1
2.2
3
4
5.5
5.5
380 –
415V
12.5
For motors with service factors less
than 1.15, multiply the motor FLA by
.90 to select appropriate MMP.
Example: For motor having FLA
of 6.4A and service factor of 1.0
(6.4A x .90 = 5.76A) select Catalog
Number XTPB6P3B01.
See Application Note — AP03402001E.
0.06
0.09
0.12
0.25
0.55
0.75
1.5
2.2
4
5.5
7.5
9
For more information visit: www.eaton.com
IEC Contactors & Starters
XT IEC Power Control
Manual Motor Protectors
440V
11
12.5
0.06
0.12
0.18
0.25
0.55
1.1
1.5
3
4
5.5
9
500V
12.5
15
0.06
0.12
0.25
0.37
0.75
1.1
2.2
3
4
5.5
9
660 –
690V
11
12.5
15
22
0.06
0.12
0.18
0.25
0.55
1.1
1.5
3
4
7.5
Maximum hp Rating — P (hp)
UL 508/CSA C 22.2 No. 14
3-Phase
200V
1
1-1/2
3
3
3
5
5
1/2
240V
1
1-1/2
3
3
5
5
7-1/2
1/2
For motor with service factor of 1.15
or greater, use motor nameplate Full
Load Amperes to select the appropriate
MMP.
Example: For motor having FLA of 11A
and service factor of 1.15, select Cata-
log Number XTPR012BC1.
Technical Data . . . . . . . . . . . . . . . . . . Page 34-142
Discount Symbol . . . . . . . . . . . . . . . . 1CD7
480V
10
10
15
1
2
3
7-1/2
7-1/2
1/2
3/4
600V
10
10
10
15
20
1
1-1/2
3
5
1/2
Screw Terminals
Catalog
Number
XTPBP16BC1
XTPBP25BC1
XTPBP40BC1
XTPBP63BC1
XTPB001BC1
XTPB1P6BC1
XTPB2P5BC1
XTPB004BC1
XTPB6P3BC1
XTPB010BC1
XTPB012BC1
XTPB016BC1
XTPB020BC1
XTPB025BC1
Price
U.S. $
34-125