1090-2000-1 EUROTHERM CONTROLS, 1090-2000-1 Datasheet

Isolation Amplifier

1090-2000-1

Manufacturer Part Number
1090-2000-1
Description
Isolation Amplifier
Manufacturer
EUROTHERM CONTROLS
Datasheet

Specifications of 1090-2000-1

Width
2.85"
Output Accuracy
± 0.01%
Signal Input Type
Selectable Current Or Voltage
Configuration Setup
DIP Switch
Supply Voltage Max
240VAC
Iso-amp Mounting Type
DIN Rail
Display Alarm Type
2 Relay
Lead Free Status / RoHS Status
na
Benefits
AP1080 &
AP1090
DC Input, Field
Configurable Limit Alarms
Provides Relay Contact Closures
at a Preset DC Input Level
Field Configurable Input
and Current
Setpoints Programmable
HI or LO
Exclusive “Dynamic
False Trips
Selectable Failsafe/
LED Trip Indicators
Selectable 120/240VAC
(9 to 30 VDC Available)
Ranges for DC Voltage
Deadband” Prevents
Latching Operation
Input Power
Description
Action Pak models AP1080 single setpoint and AP1090 dual setpoint limit alarms offer flexible,
wide-ranging DC input capability. Voltage spans from 10mV to 200 volts and current spans from
1mA to 100mA can be field configured. Bipolar inputs are also accepted. Both models offer
configurable latching, failsafe and HI/LO operation. The AP1080 and AP1090 also include 0.25%-
50% adjustable deadbands and selectable 120/240VAC input power.
Diagnostic LED
Models AP1080-2000 and AP1090-2000 are equipped with a dual function diagnostic LED. The green
center LED indicates line power and input signal status. Active line power is indicated by an illuminated
LED. If the center LED is off, check line power and the wiring connection. If the input signal is above
100% full scale, the LED will flash at approximately 8Hz. Below 0%, the flash rate is approximately
4Hz.
Output Selection
The single setpoint AP1080 and the dual setpoint AP1090 provide the following relay outputs:
AP1080
AP1090
Setpoints are top accessed multi-turn potentiometers or option "P" provides top mounted ten-turn
dials.
Operation
The field configurable AP1080 and AP1090 limit alarm setpoints can be configured for HI, LO,
latching or failsafe trip operation. Non-latching HI and LO setpoints have respective HI and LO
deadbands. In a tripped condition, the setpoint is exceeded and the appropriate red LED will
illuminate. The trip will reset only when the process falls below the HI deadband or rises above the
LO deadband (see figure 1). To reset a latched setpoint the signal must be in the safe region and the
line power turned off for at least 5 seconds. For proper deadband operation, a HI setpoint must
always be set above a LO setpoint.
In failsafe operation, the relay is energized when the process is below the HI setpoint or above the
LO setpoint (opposite for non-failsafe). In the failsafe mode, the relays go to the tripped condition
when the power fails.
Single Trip (DPDT, 5A)
Single/Dual Trip (2 SPDT, 5A)
®

Related parts for 1090-2000-1

1090-2000-1 Summary of contents

Page 1

... Setpoints are top accessed multi-turn potentiometers or option "P" provides top mounted ten-turn dials. Operation The field configurable AP1080 and AP1090 limit alarm setpoints can be configured for HI, LO, latching or failsafe trip operation. Non-latching HI and LO setpoints have respective HI and LO deadbands tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate ...

Page 2

... Note that Custom Calibration (option C620) is available from the factory (settings MUST be within specifications): a) Setpoint A: Type (HI/LO); Units (mA, mV, V); Deadband (%) b) Setpoint B (1090 only): Type (HI/ LO); Units (mA, mV, V); Deadband (%) c) Latching (ON/OFF) d) Failsafe (ON/OFF) 2000 Input Ranges *Note: Use Jumper (W2) to configure either voltage or current input ...

Page 3

... Figure 2: DC Inductive Loads Figure 4: AP1090-2000 Factory Calibration 0-20mA, Dual HI/LO, Non- Latching, Non-Failsafe. Unipolar ON "A" HI Trip ON Bipolar OFF "A" LO Trip OFF Figure 6: Mode Selection Dual Trip/A: HI, B: LO, Non-Latching, Non-Failsafe *AP1090-2000 only. Figure 3: AC Inductive Loads "B" HI Trip ON Latching ON "B" LO Trip ...

Page 4

... For additional information on calibration, operation and installation contact our Technical Services Group: 721-0479-00-M 09/04 Copyright© Eurotherm, Inc 2004 Barber-Colman Eurotherm Chessell Relay Contacts AP1080: DPDT (2 Form C) AP1090: 1 SPDT (1 Form C) per setpoint Current Rating (resistive) 120VAC: 5A; 240VAC: 2A; 28VDC: 5A Material: Silver-Cadmium Oxide Electrical Life operations at rated load Note: External relay contact protection is required for use with inductive loads ...

Related keywords