CV500-ZS3AT1-EV2 Omron, CV500-ZS3AT1-EV2 Datasheet - Page 48

no-image

CV500-ZS3AT1-EV2

Manufacturer Part Number
CV500-ZS3AT1-EV2
Description
C.V SOFTWARE 3.5in DISK
Manufacturer
Omron
Datasheet

Specifications of CV500-ZS3AT1-EV2

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Rack Components
CV500-PS221/CVM1-PA208
CV500-PS211
Terminals for external
connections
Terminals for external
connections
POWER Indicator
Lights when power
is supplied.
POWER Indicator
Lights when power
is supplied.
Note When complying with EC Directives (low voltage), use rein-
NC
NC
NC
NC
forced insulation or double insulation on the DC power supply.
DC input
START input
RUN output
AC input
START input
RUN output
Connect a 24-VDC power source.
Short the
terminal to improve noise immunity and
prevent electric shock.
Ground this terminal at a resistance of
less than 100
Use an independent ground not shared
with other equipment.
These terminals are short-circuited at
the factory. Remove the sort-circuit
bracket to allow enabling and disab-
ling of the PC with an external signal
(input: 24 VDC, 10 mA). Normally,
leave them short-circuited. These ter-
minals are used on CPU Racks only.
These terminals are turned ON during RUN
operation.
Maximum Switching Capacity:
250 VAC: 2 A (resistive load, cosf = 1)
250 VAC: 0.5 A (inductive load, cosf = 0.4)
24 VDC: 2 A
Maximum Switching Capacity when Meeting
EC Directives (Low-voltage Directives):
24 VDC: 2 A
Connect a 100 to 120-VAC or 200 to
240-VAC power source.
Short the
terminal to improve noise immunity and
prevent electric shock.
Ground this terminal at a resistance of
less than 100
Use an independent ground not shared
with other equipment.
These terminals are short-circuit at
the factory. Remove the sort-circuit
bracket to allow enabling and disab-
ling of the PC with an external signal
(input: 24 VDC,10 mA). Normally,
leave them short-circuited. These ter-
minals are used on CPU Racks only.
These terminals are turned ON during RUN
operation.
Maximum Switching Capacity:
250 VAC: 2 A (resistive load, cosf = 1)
250 VAC: 0.5 A (inductive load, cosf = 0.4)
24 VDC: 2 A
(LG) terminal to the
(LG) terminal to the
to prevent electric shock.
to prevent electric shock.
Section 2-3
(GR)
(GR)
35