Error Messages and Alarm Outputs
Fatal Errors (cont’d)
78
Power interruption
Expansion CPU
Rack power OFF
CPU error
Memory error
I/O bus error
Duplicated
number
CPU bus error
I/O points over
I/O setting error
Program error
Cycle time over
Fatal SFC error
System failure
(FALS)
Item
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
output
RUN
Note *0 through 7 indicate rack numbers; E indicates series 0; F indicates series 1.
None
None
None
A40115 ON
A40114 ON
A40113 ON
A40112 ON
A40411 ON
A40110 ON
A40109 ON
A40108 ON
A40107 ON
A40106 ON
Error flags
**00 through 15 indicate unit numbers.
***101 through 2FF indicate FALS numbers.
A012 to A013 (Power In-
terruption Time)
A014 (Number of Power
Interruptions)
None
None
A403 (Memory Area Er-
ror Location)
AR404 (I/O Bus Error
Rack and Slot Numbers)
A409 (Duplicate Rack
Number)
A410 (CPU Bus Unit Du-
plicate Number)
A405 (CPU Bus Unit Er-
ror Unit Number)
A407 (Total I/O Words
on CPU and Expansion
Racks)
A408 (Total SYSMAC
BUS/2 I/O Words)
A478 (Total SYSMAC
BUS I/O Words)
None
None
A462/463 (Maximum
Cycle Time)
A464/465 (Present
Cycle Time)
A414 (SFC Fatal Error
Code)
None
Auxiliary Area data
Error data
None
None
80FF
80F1
80C0-
80C7
(*)
80CE,
80CF
80E9
8100-
8115
(**)
80E1
80E0
80F0
809F
80F3
C101 to
C2FF
(***)
Error
code
Check the supply voltage, the
Power Supply Unit wiring, and the
defined power interruption time.
Turn on the power to the Expan-
sion CPU Rack.
Turn the power OFF and ON
again.
Check/correct the program. Cor-
rectly mount the Memory Card
and Expansion DM Unit. Check
the battery connection. Perform
the error clear operation after cor-
rective actions have been taken.
Check the cables between the
Racks. Perform the error clear op-
eration after corrective action has
been taken.
Set the Rack No. and Unit No.
again. Then turn the power OFF
and ON again. Perform the error
clear operation after corrective
action has been taken.
Check the cables between the
CPU Rack and Expansion CPU
Rack. Perform the error clear op-
eration after corrective actions
have been taken.
Read the I/O table to check the
number of words allocated. Cor-
rect the table if necessary by
creating a new one.
Verify the I/O table. Correct the
table if necessary.
Correct the program. Perform the
error clear operation after correc-
tive actions have been taken.
Check the program or set time for
monitoring the cycle.
Correct the program. Perform the
error clear operation after correc-
tive actions have been taken.
Check/correct the program.
Corrective action
Section 5-1