The information below indicates various symptoms a user may encounter in the event the S4K5U
develops a problem. Use this information to determine whether external factors caused the problem
and how to remedy the situation.
1. 1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. 2. An alarm will sound, alerting that the UPS requires attention.
3. 3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic
Table 3
Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is
operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Sola/Hevi-Duty representative or contact the Sola/
Hevi-Duty Technical Support Services. Please have the UPS model number and serial number avail-
able at the time of your inquiry.
All LEDs
A LED
B LED
C LED
D LED
E LED
A&C LEDs
C&E LEDs
Battery LED Flashing
A&E LEDs
B&C
B&D
D&E
ROUBLESHOOTING
aid to the operator, as described below:
LED status
Indicator meanings
On bypass due to output overload; beep every half-second
On bypass due to overtemperature condition; beep every 4 sec.
On bypass due to DC bus overvoltage; beep every 4 sec.
DC-DC failure during battery mode; beep every 4 sec.
On bypass due to PFC failure; beep every 4 sec.
On bypass due to inverter failure; beep every 4 sec.
UPS failed battery test; long beep every minute
UPS shutdown due to command from communication port (SNMP); no beep
Internal Battery source not available (continuous horn). Check Battery connection,
completely power down and reboot UPS.
Fan locked
REPO active. UPS cannot run with REPO loop open.
UPS is OFF due to previous REPO shutdown. Autorestart disabled.
Charger Malfunction
AC INPUT
AC
BAT
29
Diagnosis/Audible alarm
ON
BYPASS
Fault
Example shows UPS
on bypass because
of output overload,
signified by amber
load indicator.
Troubleshooting