MINI-SYS-PS-100-240AC/24DC/1.5 Phoenix Contact, MINI-SYS-PS-100-240AC/24DC/1.5 Datasheet

no-image

MINI-SYS-PS-100-240AC/24DC/1.5

Manufacturer Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Description
POWER SUPPLY PRIMARY SWITCH MODE
Manufacturer
Phoenix Contact

Specifications of MINI-SYS-PS-100-240AC/24DC/1.5

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
65Hz
Output Voltage
24VDC
Output Current
1.5A
Input Voltage
85V To 265V
Supply Voltage
RoHS Compliant
No. Of Outputs
1
Supply Voltage Typ
110V AC /
Rohs Compliant
Yes
MINI-SYS-PS-100-240AC/24DC/1.5
Power supply unit, primary switched-mode
INTERFACE
Data Sheet
102050_01_en
Description
With the MINI-SYS-PS power supply, additional modules
can be supplied with 24 DC using the optional DIN rail con-
nectors. The low design depth of 95 mm is a particular ad-
vantage for use in surroundings with a low height. The sys-
tem power supply particularly simplifies the power supply of
the FO transmission system PSI-MOS as well as of the ana-
log 6 mm MCR measuring transducer. In this way it empha-
sizes the seamless character of the INTERFACE product
range.
Even without the DIN rail connector, the flat power supply
unit 24 V/1.5 A is suitable for many applications in areas in
which space is restricted, as the housing is 12 mm flatter
than other comparable solutions.
Danger!
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Make sure you always use the the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
© PHOENIX CONTACT - 11/2006
The electronic short circuit and idling-proof device is con-
nected to single-phase AC networks with nominal voltages of
100 V AC to 240 V AC or to two of the phase conductors of
three-phase networks with a linked voltage of this value. In
the event of a malfunction, the output voltage is limited to
30 V DC.
Due to the U/I characteristic curve with POWER BOOST,
miniature circuit breakers blow reliably. For function monitor-
ing, there is the floating DC OK output and the DC OK LED.
High operational reliability is provided by the mains failure
bridging time of more than 20 ms under full load.
Ambient temperatures can be in the range of -25°C to +70°C,
whereby the power reserve of approx. 25% up to 40°C is per-
manently available.

Related parts for MINI-SYS-PS-100-240AC/24DC/1.5

MINI-SYS-PS-100-240AC/24DC/1.5 Summary of contents

Page 1

... MINI-SYS-PS-100-240AC/24DC/1.5 Power supply unit, primary switched-mode INTERFACE Data Sheet 102050_01_en Description With the MINI-SYS-PS power supply, additional modules can be supplied with 24 DC using the optional DIN rail con- nectors. The low design depth particular ad- vantage for use in surroundings with a low height. The sys- ...

Page 2

... Ascent time Residual ripple Peak switching voltages Connection in parallel Surge protection against internal surge voltages Resistance to reverse feed 102050_01_en MINI-SYS-PS-100-240AC/24DC/1.5 Type Order No. MINI-SYS-PS-100-240AC/24DC/1.5 2866983 Type Order No. ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 100 V AC ... 240 ... 264 ... 65 Hz Approx. 0.75 A (120 V AC) Approx ...

Page 3

... Climatic data Ambient temperature (operation) Ambient temperature (storage/transport) Max. permissible. relative humidity (operation) Vibration (operation) Shock Pollution degree in acc. with EN 50178 Climatic class 102050_01_en MINI-SYS-PS-100-240AC/24DC/1.5 U > 21.5 V: Contact closed OUT AC/DC LED green (U > 21,5 V DC: LED permanently lit) out EN 60204 ...

Page 4

... Comments Criterion B Input/Output/Signal Level 3 - asymmetrical Frequency range 0.15 MHz ... 80 MHz Voltage 10 V Comments Criterion A Input (mains buffering > 20 ms) Comments Criterion B EN 55011 (EN 55022) Class B, area of application: Industry and residential EN 55011 (EN 55022) Class B, area of application: Industry and residential MINI-SYS-PS-100-240AC/24DC/1.5 PHOENIX CONTACT 4 ...

Page 5

... Hz ... 65 Hz 3.15 A (slow-blow, internal (power circuit-breaker, characteristic (power circuit-breaker, characteristic (power circuit-breaker, characteristic B) COMBICON screw/plug connection ±1% 1.5 A (up to 60° (with POWER BOOST) COMBICON screw/plug connection 7 mm MINI-SYS-PS-100-240AC/24DC/1.5 2 [mm ] AWG [Nm] solid stranded Torque 0.2 - 2.5 0 0.5 - 0.6 0.2 - 2.5 0 ...

Page 6

... All output lines are dimensioned according to the maximum output current of the device or separately protected! Sufficient convection is guaranteed! Installation 102050_01_en MINI-SYS-PS-100-240AC/24DC/1.5 In order to guarantee sufficient convection, we recommend observing the following minimum distance to other modules vertical di- rection and horizontal direction. The power supply unit can be snapped onto all DIN rails in acc ...

Page 7

... Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward moti1on. Dismantling Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail. MINI-SYS-PS-100-240AC/24DC/1.5 PHOENIX CONTACT 7 ...

Page 8

... The primary side line protection, for example, is suitable. For device protection, there is an internal fuse. Additional device protection is not necessary. Recommended backup fuse for mains protection Power circuit-breaker characteristic B (or identical function). MINI-SYS-PS-100-240AC/24DC/1 ...

Page 9

... V. Signals and ohmic loads and currents can be connected. For heavily inductive loads such as a relay, a suitable protection circuit (e.g. damping diode) is necessary. MINI-SYS-PS-100-240AC/24DC/1.5 Make sure that all output lines are dimen- sioned according to the maximum output cur- rent or are separately protected. The cables on ...

Page 10

... Kelvin increase in temperature. The de- vice does not switch off at ambient temperatures of +70°C or thermal overload. The output capacity is reduced as far as necessary to provide device protection. After it has cooled down, the output capacity is increased again. 60 MINI-SYS-PS-100-240AC/24DC/1 the case of ambi- N PHOENIX CONTACT 10 ...

Page 11

... Otherwise the consumers should be spread among individual devices independent of one another. A maximum of five devices can be connected in parallel! Σ − Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3 www.phoenixcontact.com MINI-SYS-PS-100-240AC/24DC/1.5 . Parallel connection to increase efficiency N PHOENIX CONTACT 11 ...