MINI-SYS-PS-100-240AC/24DC/1.5 Phoenix Contact, MINI-SYS-PS-100-240AC/24DC/1.5 Datasheet - Page 11

no-image

MINI-SYS-PS-100-240AC/24DC/1.5

Manufacturer Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Description
POWER SUPPLY PRIMARY SWITCH MODE
Manufacturer
Phoenix Contact

Specifications of MINI-SYS-PS-100-240AC/24DC/1.5

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
65Hz
Output Voltage
24VDC
Output Current
1.5A
Input Voltage
85V To 265V
Supply Voltage
RoHS Compliant
No. Of Outputs
1
Supply Voltage Typ
110V AC /
Rohs Compliant
Yes
102050_01_en
+
+
I
I
N
N
+
+
+
+
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
I
I
N
N
Σ
Σ
= 2 x I
= I
www.phoenixcontact.com
+
+
N
N
Parallel operation
Due to the current carrying capacity, a maximum of two de-
vices may be connected in parallel on the DIN rail connector
for redundancy. Without using the DIN rail connector, de-
vices of the same type can be connected in parallel both for
redundancy reasons as well as to improve performance.
To ensure symmetrical distribution of power, we recommend
designing all cable connections from the power supply unit to
a busbar of the same length and with the same conductor
cross section. The system makes it advisable to install a pro-
tective circuit at the output of each device when more than
two power supply units are connected in parallel (e.g. decou-
pling diode or DC fuse). This prevents high reverse feed cur-
rents in the event of a secondary device fault.
Redundant operation
Redundant circuits are suitable for the supply of systems
which make especially high requirements on the operational
safety. If a fault occurs in the primary circuit of the first power
supply unit, the second device automatically takes over the
entire power supply, without interruption, and vice versa. For
this reason, the power supply units to be connected in paral-
lel are dimensioned in such a way that the total current re-
quirement of all consumers can be completely covered by
one power supply unit. 100% redundancy makes external
decoupling diodes necessary (QUINT-DIODE/40, Order No.
2938963)!
Increased performance
For n parallel connected devices, the output current can be
increased to n x I
is used for the expansion of existing systems. It is advisable
to use parallel connection if the power supply unit does not
cover the current requirement of the most powerful con-
sumer. Otherwise the consumers should be spread among
individual devices independent of one another. A maximum
of five devices can be connected in parallel!
N
. Parallel connection to increase efficiency
MINI-SYS-PS-100-240AC/24DC/1.5
PHOENIX CONTACT
11

Related parts for MINI-SYS-PS-100-240AC/24DC/1.5