QO112M100 SQUARE D, QO112M100 Datasheet - Page 9

CIRCUIT BREAKER, LOAD CENTER, 240V, 100A

QO112M100

Manufacturer Part Number
QO112M100
Description
CIRCUIT BREAKER, LOAD CENTER, 240V, 100A
Manufacturer
SQUARE D
Series
QOr
Datasheet

Specifications of QO112M100

Supply Voltage
240VAC
Current Rating
100A
No. Of Branch Circuits
12
External Depth
3.75"
External Height
17.92"
External Width
14.25"
Enclosure Material
Steel
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
03/2007
Top or bottom mains positioning. Rotate
entire load center 180 degrees.
Main Circuit Breaker
Main Lug
Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains
UL Listed
Short Circuit Current Rating
Interior
Mains
Factory-installed main lugs convertible to main circuit breaker
Factory-installed main circuit breaker convertible to main lugs
Main Circuit Breaker Amperage
QO
File E-6294
Federal Specification W-P-115c, Type 1, Class 2
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 20)
Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of
branch circuit breakers installed)
Main circuit breaker: 22,000 AIR standard
22,000 AIR main circuit breaker kits (refer to page 10 and Technical
Information on page 20)
Shielded, one-piece tin plated copper bus
Removable interior with single, captive mounting screw
Split branch neutral with up to 50% more terminations than required
Multiple mounting locations for equipment grounding bar kits: left, right,
and bottom
Main lugs load centers have equipment grounding bar kits included (not
factory-installed)
®
Load Center Amperage
and Homeline
100
125
150
200
225
125
150
200
225
General Information and Application Data
© 2007 Schneider Electric All Rights Reserved
Main Lug Kit Amperage
®
Load Centers and Enclosures
125
125
225
225
225
Main Circuit Breaker Kit Amperage
100 15 0
100 20 0
100 22 5
Load Center Amperage
50 125
100
125
150
200
225